SITRANS LR 460 (PROFIBUS PA) – INSTRUCTION MANUAL
7ML19985JM01
mmmmm
J;
 P
rof
i;
e
 st
ruct
ur
e
 P
A
Description of the blocks
Level Transducer Block function groups
The figure below shows the signal flow of measured values from the sensor through the 
Level Transducer Block into the output value (Primary Value/ Level; Secondary Value 1 / 
Level; or Secondary Value 2 /Distance. The LTB implements all of the basic parameters 
(see parameter diagram on page 101).
1
How the Level Transducer Block works:
1.
The sensor technology block selects the proper echo. Se
72 for more detail.
The sensor value (in sensor units) is checked to see if it is within its measuring limits. 
If the limit is exceeded, this results in a Bad status and the error message Failure in 
measurement. The sensor value is stored in Sensor Value.
The analog signal from the sensor is transformed into a digital signal.
A Sensor Offset (default 0) provides compensation if necessary for differences 
between the vessel reference point and the sensor reference point.
Note: Primary Value (PV) is the default measured value; Secondary Value 1 (SV1) is an 
equivalent value.
1.
A Linearization module is required by the PROFIBUS PA specifications. The 
Linearization block is turned off in SITRANS LR 460. 
Level Transducer Block
Sensor Value 
(sensor units)
Sensor
Sensor 
technology
Level 
calibration
Linearization 
(turned off)
Level
(level units)
Primary Value
Level
(level units)
(Analog 
Input)
AIFB1
Secondary Value 1 
[Level]
(Level Units)
Secondary Value 2 
[Distance]
(Sensor Units)
Sensor 
Offset
Level 
Offset
High 
Calibration 
Point
High Level 
Point 
Low 
Calibration 
Point 
Low Level 
Point
Calibration 
Type
Linearization 
Type
PV
SV1
SV2
AIFB2
(Analog 
Input)