Heatcraft Refrigeration Products GLC Benutzerhandbuch

Seite von 20
4
Performance Data
Model RLC
 Air Defrost | 60 Hz
Model
Capacity
Fan Data
10°F TD
25°F SST
6°C TD
-4°C SST
No. 
CFM 
m
3
H
BTUH
Watts
RLC040
4,000
1,170
1
730
1,240
RLC052
5,200
1,520
1
700
1,189
RLC065
6,500
1,900
1
650
1,104
RLC070
7,000
2,050
2
1,460
2,481
RLC090
9,000
2,640
2
1,400
2,379
RLC104
10,400
3,050
2
1,400
2,379
RLC120
12,000
3,500
2
1,300
2,209
RLC130
13,000
3,810
2
1,300
2,209
RLC140
14,000
4,100
3
2,100
3,568
RLC156
15,600
4,570
3
2,100
3,568
RLC180
18,000
5,270
3
1,950
3,313
RLC208
20,800
6,100
4
2,800
4,758
RLC260
26,000
7,620
5
3,250
5,522
RLC312
31,200
9,140
6
3,900
6,627
RLC370
37,000
10,840
6
3,900
6,627
Model RLC
 Air Defrost | 50 Hz 
Model
Capacity
Fan Data
10°F TD
25°F SST
6°C TD
-4°C SST
No. 
CFM 
m
3
H
BTUH
Watts
RLC040
3,800
1,112
1
670
1,117
RLC052
4,940
1,445
1
630
1,070
RLC065
6,175
1,807
1
586
995
RLC070
6,650
1,946
2
1,315
2,234
RLC090
8,550
2,502
2
1,260
2,142
RLC104
9,880
2,891
2
1,260
2,142
RLC120
11,400
3,335
2
1,170
1,989
RLC130
12,350
3,613
2
1,170
1,989
RLC140
13,300
3,891
3
1,891
3,213
RLC156
14,820
4,336
3
1,891
3,213
RLC180
17,100
5,003
3
1,756
2,984
RLC208
19,760
5,781
4
2,521
4,284
RLC260
24,700
7,226
5
2,927
4,973
RLC312
29,640
8,672
6
3,512
5,967
RLC370
35,150
10,284
6
3,512
5,967
 For EC motors, use 60 Hz capacity and airflow values (Units with EC motors operating at 50 Hz will 
not see a reduction in performance due to the electronic control of the motor)