Performance Data
Model GLC 
Hot Gas Defrost | 60 Hz
Model
Capacity
Fan Data
10°F TD
-20°F SST
6°C TD
-29°C SST
No.
CFM
m
3
H
BTUH  
Watts
6 F
ins P
er I
nch
GLC035
3,500
1,025
1
700
1,189
GLC040
4,000
1,170
1
700
1,189
GLC047
4,700
1,380
1
650
1,104
GLC065
6,500
1,900
2
1,400
2,379
GLC075
7,500
2,200
2
1,300
2,209
GLC090
9,000
2,640
2
1,300
2,209
GLC120
12,000
3,520
3
2,100
3,568
GLC140
14,000
4,100
3
1,950
3,313
GLC160
16,000
4,690
4
2,600
4,418
GLC180
18,000
5,280
4
2,600
4,418
GLC200
20,000
5,860
5
3,250
5,522
GLC240
24,000
7,030
6
3,900
6,627
GLC280
28,000
8,200
6
3,900
6,627
4 F
ins P
er I
nch
GLC041
4,100
1,200
1
690
1,172
GLC068
6,800
2,000
2
1,380
2,345
GLC080
8,000
2,340
2
1,380
2,345
GLC102
10,200
2,990
3
2,170
3,687
GLC136
13,600
3,990
4
2,760
4,690
GLC170
17,000
4,980
5
3,450
5,862
GLC204
20,400
5,980
6
4,140
7,035
GLC235
23,500
6,880
6
4,140
7,035
Model GLC
 Hot Gas Defrost  | 50 Hz 
Model
Capacity
Fan Data
10°F TD
-20°F SST
6°C TD
-29°C SST
No.
CFM
m
3
H
BTUH  
Watts
6 F
ins P
er  I
nch
GLC035
3,325
974
1
630
1,070
GLC040
3,800
1,113
1
630
1,070
GLC047
4,465
1,308
1
586
995
GLC065
6,175
1,809
2
1,260
2,142
GLC075
7,125
2,087
2
1,170
1,989
GLC090
8,550
2,504
2
1,170
1,989
GLC120
11,400
3,339
3
1,891
3,213
GLC140
1,950
3,313
3
1,756
2,984
GLC160
2,600
4,418
4
2,341
3,978
GLC180
2,600
4,418
4
2,341
3,978
GLC200
3,250
5,522
5
2,927
4,973
GLC240
3,900
6,627
6
3,512
5,967
GLC280
3,900
6,627
6
3,512
5,967
4 F
ins P
er I
nch
GLC041
690
1,172
1
621
1,056
GLC068
1,380
2,345
2
1,243
2,111
GLC080
1,380
2,345
2
1,243
2,111
GLC102
2,170
3,687
3
1,954
3,320
GLC136
2,760
4,690
4
2,485
4,223
GLC170
3,450
5,862
5
3,107
5,279
GLC204
4,140
7,035
6
3,728
6,334
GLC235
4,140
7,035
6
3,728
6,334
 For EC motors, use 60 Hz capacity and airflow values (Units with EC motors 
operating at 50 Hz will not see a reduction in performance due to the electronic 
control of the motor)
NOTE: When using the hot gas units with a hot gas 
loop drain pan on 0°F applications and below, an 
insulated drain pan is required.
Capacity Correction Factors For 
Electric and Hot Gas Defrost Units
Saturated Suction 
Temperature °F
+20
-10
-20
-30
Saturated Suction 
Temperature °C
-7
-23
-29
-34
Multiply Capacity 
By