AVOID FIRE:  To ensure  that insulation or any  other combustible 
material does not contact the chimney, a chimney inside the house 
must have at least 2 inches (51mm) of air space clearance around 
the chimney.  A chimney outside the house must have at least 1 
inch (25mm) clearance to the combustible structure.  Non-combus-
tible fire stops must be installed at the spaces where the chimney 
passes through floors and/or ceilings.  
Refer to Figures 7.1 & 7.2 
on  page  7.    Canadian  installations  require  a  full  reline  of  the 
chimney.
CHIMNEY HEIGHT/DRAFT
T
o be sure that your Quadra-Fire insert burns properly, the chimney 
draft (static pressure) should be approximately -0.10 inches water 
column (W.C.) during a high burn and -0.04 inches W.C. during a 
low burn, measured 6 inches (152mm) above the top of the insert 
after one hour of operation at each burn setting.
NOTE:  These are guidelines  only, and  may vary somewhat  for 
individual installations.
Your Quadra-Fire insert was designed for and tested on a 6 inch 
(152mm) chimney, 12 ft-14 ft (60-420cm) high, measured from 
the  base  of  the  insert.    In  addition,  exterior  conditions  such  as 
roof line, surrounding trees, prevailing winds and nearby hills can 
influence insert’s performance.  Your local dealer is the expert in 
your geographic area and can usually make suggestions or discover 
solutions that will easily correct your flue problem.
A masonry chimney or a listed factory-built UL10 HT Class “A” 
chimney must be the required height above the roof and any other 
nearby obstructions.  The chimney must be at least  ft (91cm) higher 
than the highest point where it passes through the roof and at least 
2 ft (61cm) higher than the highest part of the roof or structure that 
is within 10 ft (05cm) of the chimney, measured horizontally.  
See 
2-10-3 Rule (Figure 5.1).  These are safety requirements and 
are not meant to assure proper flue draft.
ft Min 
(91cm) 
2 ft Min (61cm) 
10 ft Min 
(05cm) 
2-10-3 RULE 
Figure 5.1
NOTE: Clearances may only be reduced by means approved by 
the regulatory authority having jurisdiction.
WE  RECOMMEND  that  a  qualified  building  inspector  and  your 
insurance  company  representative  review  your  plans 
before 
installation.
INSTALLATION RECOMMENDATIONS
The  Quadra-Fire  2700-I  Insert  has  met  and  surpassed  the  most 
stringent emissions standards in the United States.  The sophistica-
tion of the interior firebox design requires that a proper draft be sup-
plied by the chimney, therefore adherence to the following factors 
will enable your insert to operate at its optimum capability.
REqUIRED:  Direct connection to the first flue liner in accordance 
with  the  requirements  of  the  NFPA  211.  In  USA  a  full  chimney 
liner for factory-built fireplaces is recommended but is required in 
Canada.
BEST:    A  complete  relining  of  the  chimney  system  with  a  6  inch 
(152mm)  diameter  listed,  stainless  liner.    Required  for  factory-built 
fireplace installations in Canada, recommended in USA. The sections 
must  be  attached  to  the  insert  and  to  each  other  with  the  crimped 
(male) end pointing toward the insert.  See 
Figure 5.2.   All joints, 
including  the  connection  at  the  flue  collar,  should  be  secured  with 
three sheet metal screws.  Make sure to follow the minimum clear-
ances to combustibles as set out on 
page 4 of the manual.
These installation instructions describe the installation and opera-
tion of the Quadra-Fire 2700-I Wood Insert.  This insert meets the 
U.S. Environmental Protection Agency’s 1990 particulate emission 
standards.  The 2700-I is listed by OMNI-Test Laboratories, Inc.  
(Report No. 061-S-52-2), to UL Safety Standard 1482, and ULC 
S628-9, and (UM) 84-HUD. The 2700-I is approved for mobile 
home installations when not installed in a sleeping room and when 
an outside combustion air inlet is provided.  The structural integrity 
of the mobile home floor, ceiling, and walls must be maintained.  
The insert must be properly grounded to the frame of the mobile 
home.  
Check with your local building code agency before you begin your 
installation to ensure compliance with local codes, including the 
need for permits and follow-up inspections.  Be sure local building 
codes do not supersede UL specifications.  Always obtain a building 
permit so that insurance protection benefits cannot be unexpectedly 
cancelled.  If any assistance is required during installation, please 
contact your local dealer.
LISTINGS
CHIMNEY HEIGHT/DRAFT
 (CONT’D)
Figure 5.2
Fire Risk.
•  Comply with all minimum clearances to 
combustibles as specified.
•  Failure to comply may cause house fire.
WARNING
LINER CONNECTOR
FLUE
 GAS 
DIRECTION
CRIMPED
END
TOWARDS 
STOVE