1. Specifications
1-5
Refrigerant Flow Diagram
Outdoor Unit: CH2432
Indoor Unit: XHS2432
1-6
Operating Range
Temperature
Indoor Air Intake
Outdoor Air Intake
Cooling
Maximum
95 
°
F DB, 71 
°
F WB
115 
°
F DB
Minimum
67 
°
F DB, 57 
°
F WB
23 
°
F DB
Heating
Maximum
80 
°
F DB, 67 
°
F WB
75 
°
F DB, 65 
°
F WB
Minimum
-DB / -WB
17 
°
F DB / 15 
°
F WB
HP
High
pressure
switch
Compressor
Accumulator
Accumulator
EC
P
Heat exchanger
4-way valve
EC
P
Heat exchanger
Distributor
Electronic
ref.control
valve
Strainer
Liquid line
nipple
Liquid line
service
valve
O.D.
1/4"
(6.35mm)
O.D.
3/4"
(19.05mm)
Gas line
nipple
Gas line
service
valve
Distributor
Sub-heat exchanger
Cooling Cycle
Heating Cycle
Strainer
M
1132_THS_I
Muffler