2. Processes and functions
(B) Heating
Chart Summary and Explanations
Once the compressor starts, it keeps running for 5 minutes.
Once the compressor stops, it will not start running again for 3 minutes.
If you change the operation mode (HEAT, COOL or FAN) during the heating cycle, the
control circuit stops the compressor for 3 minutes.
For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off,
the compressor is not controlled by the room sensor.
When set on remote control sensor
Thermo ON: When room temperature is –2°F below the set temperature T˚.
Compressor   
  ON
Thermo OFF: When the room temperature is 2°F above the set temperature T˚, (T˚+2°F)
Compressor   
   OFF
When set on body sensor
NOTE: In case of Body sensor, operating temperature is shifted to setting temperature +7°F.
Fig. 2
THERMO.  ON
THERMO.  ON
+2
°
F
OFF
OFF
2
1.  Refer  to  2-4  Outdoor Fan Speed Control
OFF
SET SPEED
ON
ON
ON
ON (REVERSING CYCLE)
ON
TEMP.
OPERATION
REMOTE CONTROL 
SENSOR
(Only for wireless 
remote controller)
BODY SENSOR
OFF
OFF
SET SPEED
SET SPEED
3 SECONDS
ON
OFF
ON
MORE THAN
3 MINUTES
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
3 MINUTES
MORE THAN
5 MINUTES
5 MINUTES
THERMO.  ON
THERMO.  ON
THERMO.  ON
THERMO.  ON
2.  Refer  to  2-2  Cold Draft Prevention (Heating)
BUTTON
COIL (4-WAY)
SOLENOID
E2
TEMP.
COIL
EXCH.
INDOOR HEAT
STANDBY
2
INDOOR FAN
1
OUTDOOR FAN
(H OR M)
COMPRESSOR
SET. +2
°
F
SET. –2
°
F
–2
°
F
SET TEMP.+7
°
F SHIFT
THERMO.  OFF
THERMO.  OFF
OFF
(88
°
F)
81
°
F
77
°
F
1134_THS_I
THERMO.  OFF
THERMO.  OFF
LL
LL
LL
L
L
SETTING TEMP.
SET TEMP.