2. Processes and functions
2-11
4-Way Valve, Solenoid Control
The basic function of the 4-way valve is to direct the refrigerant in the correct direction
according to the Operation Mode (COOLING or HEATING) selected.
The following two charts show conditions of the controls and functions listed in the left hand
column when the solenoid is ON or OFF. Chart (A) on this page shows the relationships when
the temperature control is in NORMAL mode, and Chart (B) on the next page shows the
relationships when the remote controller is set to AUTO mode.
(A) Normal Control Mode
Fig. 15
OFF
OFF
OFF
OFF
OFF
3 MINUTES
OFF
TURN ON
TURN OFF
THERMO OFF
THERMO 
ON
THERMO OFF
THERMO 
ON
2
2
2
1
1
1
1
OFF
SOLENOID COIL
(4-WAY VALVE)
COMPRESSOR
COOL
MODE
BUTTON HEAT
OPERATION
BUTTON  
POWER SOURCE
1. . . More than 5 minutes
2. . . More than 3 minutes
ON
ON
HEAT
ON
ON
ON
HEAT
COOL
ON
ON
ON
ON
0443_M_S
Chart Summary and Explanations
For the first 3 minutes after power is applied, the 4–way valve remains OFF and the
compressor will not operate, even if the ON button is pushed.
If the 4–way valve is turned OFF with the compressor operating, the air conditioner
operates in COOLING mode. See Table below.
If the 4–way valve is turned ON with the compressor operating, the air conditioner operates
in HEATING  mode. See Table below.
Operation Mode
4-way valve        
Compressor
solenoid
COOLING
    OFF
ON
HEATING
    ON