4. Service procedures
1
2
3
4
Section
– 88 –
SM830076
(2)
Checking the Protective Devices
Disconnect the connector, which consists of P (plug) and S (socket) when you want to
check the protective device.
Then check continuity among plug’s (and/or socket’s) terminal as in Fig. 25.
Normality of the protective device can be judged by the following table.
The Protective Device is proved normal if there is a continuity between terminals.
1
1
1
1
1
Indoor fan motor thermal protector (49FI)  . . . . . . Indoor unit
Disconnect the connector which leads to the indoor fan motor (FMI).
Check the socket’s terminals.
2
2
2
2
2
Compressor motor thermal protector  . . . . . . Outdoor unit
Disconnect the wires from terminals of compressor.
Check the terminals of compressor.
3
3
3
3
3
Outdoor fan motor thermal protector (49FO)  . . . . . . Outdoor unit
Disconnect both the connector which leads to the outdoor fan motor (FMO).
Check socket’s terminal.
Ω
socket
Multimeter
0642_X_S
Fig. 25