York R-410A ZH/ZJ/ZR Series Benutzerhandbuch

Seite von 206
528150-YTG-G-1210
100
Johnson Controls Unitary Products
Additional Static Resistance - ZH037 thru 061
Size
(Tons)
Model
CFM Cooling Only
1
1. Add these values to the available static resistance in the respective Blower Performance Tables.
Economizer
2
 
3
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct 
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
4” Pleated Filter
2
Electric Heat kW
2
3
6
9
15
20
24
037 (3)
049 (4)
ZH
900
0.05
-0.05
0.01
0.00
0.00
0.00
0.01
0.01
0.01
1000
0.05
-0.03
0.02
0.00
0.00
0.00
0.02
0.02
0.02
1100
0.04
-0.02
0.03
0.01
0.01
0.01
0.02
0.02
0.02
1200
0.04
0.00
0.04
0.01
0.01
0.01
0.02
0.02
0.02
1300
0.03
0.01
0.05
0.01
0.01
0.01
0.03
0.03
0.03
1400
0.03
0.03
0.07
0.02
0.02
0.02
0.03
0.03
0.03
1500
0.03
0.04
0.08
0.02
0.02
0.02
0.04
0.04
0.04
1600
0.02
0.06
0.09
0.02
0.02
0.02
0.04
0.04
0.04
1700
0.02
0.07
0.10
0.03
0.03
0.03
0.05
0.05
0.05
1800
0.01
0.08
0.11
0.03
0.03
0.03
0.05
0.05
0.05
1900
0.01
0.10
0.13
0.04
0.04
0.04
0.06
0.06
0.06
2000
0.00
0.11
0.14
0.04
0.04
0.04
0.07
0.07
0.07
061 (5)
ZH
1500
-0.01
0.13
0.07
0.02
0.02
0.02
0.04
0.04
0.04
1600
-0.01
0.14
0.08
0.02
0.02
0.02
0.04
0.04
0.04
1700
-0.01
0.15
0.08
0.03
0.03
0.03
0.05
0.05
0.05
1800
-0.02
0.16
0.09
0.03
0.03
0.03
0.05
0.05
0.05
1900
-0.02
0.17
0.10
0.04
0.04
0.04
0.06
0.06
0.06
2000
-0.02
0.18
0.10
0.04
0.04
0.04
0.07
0.07
0.07
2100
-0.03
0.19
0.11
0.05
0.05
0.05
0.07
0.07
0.07
2200
-0.03
0.20
0.12
0.06
0.06
0.06
0.08
0.08
0.08
2300
-0.04
0.21
0.12
0.06
0.06
0.06
0.09
0.09
0.09
2400
-0.04
0.22
0.13
0.07
0.07
0.07
0.10
0.10
0.10
2500
-0.05
0.23
0.14
0.08
0.08
0.08
0.11
0.11
0.11
Additional Static Resistance - ZJ/ZR037 thru 061
Size
(Tons)
Model
CFM Cooling Only
1
1. Add these values to the available static resistance in the respective Blower Performance Tables.
Economizer
2
 
3
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct 
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
4” Pleated Filter
2
Electric Heat kW
2
3
6
9
15
20
24
037 (3)
ZJ/ZR
900
0.05
-0.05
0.01
0.00
0.00
0.00
0.01
0.01
0.01
1000
0.05
-0.03
0.02
0.00
0.00
0.00
0.02
0.02
0.02
1100
0.04
-0.02
0.03
0.01
0.01
0.01
0.02
0.02
0.02
1200
0.04
0.00
0.04
0.01
0.01
0.01
0.02
0.02
0.02
1300
0.03
0.01
0.05
0.01
0.01
0.01
0.03
0.03
0.03
1400
0.03
0.03
0.07
0.02
0.02
0.02
0.03
0.03
0.03
1500
0.03
0.04
0.08
0.02
0.02
0.02
0.04
0.04
0.04
049 (4)
061 (5)
ZJ/ZR
1200
-0.01
0.10
0.05
0.01
0.01
0.01
0.02
0.02
0.02
1300
-0.01
0.11
0.06
0.01
0.01
0.01
0.03
0.03
0.03
1400
-0.01
0.12
0.06
0.02
0.02
0.02
0.03
0.03
0.03
1500
-0.01
0.13
0.07
0.02
0.02
0.02
0.04
0.04
0.04
1600
-0.01
0.14
0.08
0.02
0.02
0.02
0.04
0.04
0.04
1700
-0.01
0.15
0.08
0.03
0.03
0.03
0.05
0.05
0.05
1800
-0.02
0.16
0.09
0.03
0.03
0.03
0.05
0.05
0.05
1900
-0.02
0.17
0.10
0.04
0.04
0.04
0.06
0.06
0.06
2000
-0.02
0.18
0.10
0.04
0.04
0.04
0.07
0.07
0.07
2100
-0.03
0.19
0.11
0.05
0.05
0.05
0.07
0.07
0.07
2200
-0.03
0.20
0.12
0.06
0.06
0.06
0.08
0.08
0.08
2300
-0.04
0.21
0.12
0.06
0.06
0.06
0.09
0.09
0.09
2400
-0.04
0.22
0.13
0.07
0.07
0.07
0.10
0.10
0.10
2500
-0.05
0.23
0.14
0.08
0.08
0.08
0.11
0.11
0.11