Honeywell T7100D Benutzerhandbuch

Seite von 16
T7100D,E,F MICROELECTRONIC COMMERCIAL THERMOSTATS AND Q7100A,C,D SUBBASES
68-0163—3
10
INSTALLER SELF-TEST
Use the Installer Self-Test to check the thermostat
configurations and operation. Refer to Table 7 for a list of the
available Self-Tests.
To start the Self-Test:
NOTE:
The minimum off time for compressors is bypassed
during the Installer Self-Test.
Press and hold the increase 
 and decrease 
▼ 
keys at the
same time until two zeros appear. All segments of the LCD will
be displayed before the two zeros appear. See Fig. 15 and 16.
Fig. 15. LCD display of all segments.
IMPORTANT
Models with system and fan switches must set the
switches to the equipment that is being checked for
the equipment to operate.
Fig. 16. Test number display.
Table  7. Tests available in the Installer Self-Test.
Em HeatOffCool Auto Only
Heat Cool
OnAuto
System
Fan
Room
Outdoor
Em Ht Temporary Setting
Wait
%Humid
Aux Ht
Remote
Repl
Batt
M4844
NOTE:
Press and hold the increase 
 and decrease 
 keys
together for three seconds to exit the Self-Test. The
Self-Test times out after five minutes without any key
presses.
Thermostat Information
1. Press the Information
   i   
key to access the thermostat
information.
M6792A
TEST  NUMBER
Test  
Number
Self-Test Description
10-19
Heating equipment can be turned on and off.
20-29
Emergency heat (Q7100C only) equipment can
be turned on and off.
30-39
Cooling equipment can be turned on and off.
40-49
Fan equipment can be turned on and off.  
60-69
Keyboard key tests.
70-79
Thermostat information including date code and
software versions are displayed.
2. Press the increase 
 key to display the production date
code. The first two large digits are the month and the
third digit is the last digit of the year
(Example: 026=February 1996).
3. Press the increase 
 key again to display the software
identification code. (Example: 02 = software ID code 2).
4. Press the increase 
 key again to display the software
revision number (Example: 001=Revision number 1).
M4864
M4866
M6791
M4865
Refer to Table 8 for the directions and results of the specific tests.