T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES
60-2485—8
22
CAUTION
Equipment Damage Hazard.
Due to calibration techniques used for T874 
Thermostats with outdoor reset, the C815A Thermistor 
must be wired into the system at all times. Failure to 
do so will result in serious degradation of performance.
Service and Replacement of C815A Outdoor 
Thermistor
To check and verify thermistor operation, perform the 
following steps:
1. Disconnect wire from T terminal on subbase.
2. Measure resistance with ohmmeter across the T sub-
base wire and X subbase terminal.
3. Take outdoor temperature measurement at thermistor 
location and find correct thermistor resistance on the 
chart in Fig. 29.
4. Compare resistance on the chart with measured resis-
tance. Replace C815A if resistance varies more than 15 
percent. Contact installing dealer for packaged replace-
ment outdoor thermistor. 
Fig. 29. Thermistor resistance chart.
Features
Two of the features of the T874/Q674 include LED indicators 
and restricted setpoint.
LED Indicators
The light-emitting diodes (LED) indicators on the subbase 
light on command when something specific happens in the 
system. See Fig. 30.
Up to four different LEDs are available. The thermostat has a 
clear lens window for viewing each LED. On TRADELINE 
models, a small insert is used so the LED function desired can 
be selected. This must be done during installation.
A blank insert is factory-installed in some T874 models. To 
remove it, push both temperature setting levers to the far ends 
of the thermostat. Use index fingernail to gently pull out the 
scaleplate a fraction of an inch. Turn thermostat upside-down, 
and the blank insert falls out.
A strip of four inserts is included with TRADELINE T874. Drop 
a strip into the recessed area behind the scaleplate so 
selected LEDs show. Make sure insert is completely seated in 
recessed area. Let scaleplate pop back; then set levers to 
desired position.
• FILTER LED lights when the filter is clogged and needs 
replacement.
• CHECK LED lights when something needs to be checked 
or done to maintain efficient operation of system. See 
heating system instructions for CHECK LED meaning.
• EM. HT. LED lights when the emergency heat is operating.
• SUPL. HT. LED lights when the supplemental heat is 
operating.
• LOCKOUT LED lights when the system is shut down and 
needs maintenance.
• AUXILIARY HEAT LED lights when the auxiliary heat is 
operating.
• SERVICE or MALFUNCTION LED can have several 
meanings. Consult heating system instructions.
LEDs cannot be replaced or added in the field.
Fig. 30. T874/Q674 LED location.
Restricted Setpoint (DoD)
The Department of Defense (DoD) models are equipped with 
a restricted setpoint feature for fuel efficiency.
Fixed stops are factory-set so setpoint levers cannot be set 
above 72°F (22°C) on heating, or below 78°F (26°C) on cooling.
Applications
The T874/Q674 can be applied to standard residential 
systems for automatic or manual changeover, to commercial 
rooftop applications, or to heat pump applications.
Changeover on Standard Residential 
Systems
In a standard residential heating-cooling circuit, changeover 
between heating and cooling can be done either automatically 
or manually.
Automatic changeover is done by an AUTO position on the 
subbase system switch. See Fig. 31. When the switch is in the 
AUTO position, the thermostat automatically changes between 
heat and cool modes, depending on the indoor temperature.
THERMISTOR RESISTANCE (ohms)
C815A THERMISTOR RESISTANCE
R = 400 ohms 
±
 10% AT 77
°
F (25
°
C)
4600
4400
4200
4000
3800
3600
3400
3200
3000
2800
2600
2400
2200
2000
1800
1600
1400
1200
1000
800
600
400
200
0
-20         0         20        40        60        80        100      120       140
TEMPERATURE OF THERMISTOR (
°
F)
M1590A
80
50 60 70 80
COOL
EM.
HEAT FILTER SERV.
AUX
HEAT
M5830
LEDS