Honeywell T874 Benutzerhandbuch

Seite von 224
T874 MULTISTAGE THERMOSTATS AND Q674 SUBBASES
60-2485—8
26
Defrost Control
In some regions, during half or more of the heating season, 
the outdoor coil operates below 32°F (0°C) Frost or ice builds 
up on the outdoor coil of a heat pump similarly to the frost 
buildup in a household refrigerator. Eventually, this 
accumulation of ice interferes with efficient heat transfer from 
the outdoor air to the coil and refrigerant. Defrosting is 
occasionally required to remove this ice, and restore the heat 
pump ability to absorb heat from the air.
Defrosting
A heat pump defrosts its outdoor coil by temporarily switching 
to the cooling mode, which causes hot gas from the 
compressor to be directed to the outdoor coil instead of to the 
indoor coil so the heat pump is taking heat from the home to 
warm up the outdoor coil. Defrosting is the greatest detriment 
to heat pump efficiency.
Defrost Control Functions
Besides changing over to the cooling mode, defrosting 
requires several more control initiated actions that follow. 
OUTDOOR FAN
When defrosting has begun, it is standard practice to turn off 
the outdoor fan to speed up the melting process. A separate 
defrost relay is required to control that fan. See Fig. 37. Other 
contacts can be needed on the defrost relay to power the 
changeover valve or power part of the auxiliary heat.
Fig. 37. Outdoor fan with defrost control.
AUXILIARY HEAT DURING DEFROST
Most pump manufacturers bring on some auxiliary heat during 
defrost, although this is not a universal practice. Some rely on 
the second stage of the thermostat to call for auxiliary heat as 
needed. Since the heat pump is operating in the cooling mode 
to defrost, it is delivering cold air to the living space. Auxiliary 
heat is used to offset this cooling. It requires another normally 
open contact on the defrost relay. See Fig. 38.
Fig. 38. Auxiliary heat with defrost control.
WHEN TO DEFROST
Timely defrosting is an essential component of effective heat 
pump operation. Failure to defrost often enough permits too 
much ice to accumulate on the coil. At the very least, this hurts 
efficiency; at worst, it results in compressor damage. 
Insufficient defrosting is a condition the heat pump 
manufacturer wants very much to avoid.
A 50 percent reduction in outdoor airflow is the maximum that 
would be tolerated. So the designer of a heat pump would 
select a control point that puts the system into defrost when 
airflow through the outdoor coil approaches half its normal 
level. Restricted airflow causes a greater load on the 
compressor; the outdoor coil runs colder, suction pressure is 
lower and the motor runs hotter.
At the other end of the scale, defrosting too often hurts the 
overall energy efficiency of the system. Consider that in terms 
of heating the building, defrosting is a big loss. Not only does 
the system stop heating, but it actually moves heat out of the 
building. If electric strip heat is used, it is a further waste 
because its COP is 1.0 and not the 2.0 or more COP realized 
if the heat is provided by the heat pump.
So, concern for equipment safety suggests fairly frequent 
defrosting while economy of operation argues for fewer 
defrost cycles. Since the equipment manufacturer chooses, the 
balance is usually tipped in favor of more frequent defrosting to 
avoid the possibility of damaging the compressor.
Auxiliary Heat
Except in warm climates, all air-to-air heat pump installations 
require auxiliary heat capability. Electric resistance heaters 
can provide this auxiliary heat.
The electric heaters (sometimes called strip heaters) usually 
are supplied in 5 kW units or strips (about 17,000 Btu). The 
indoor unit of the heat pump is designed to accommodate 
various electric heat units so it can be used in variously sized 
buildings in different parts of the country.
Two-Stage Thermostat
The most common heat pump control strategy is for the 
thermostat first stage to switch the compressor and the 
second stage to switch the auxiliary heat. See Fig. 39.
M5839
COMPRESSOR 
MOTOR
CONTACTOR
CONTROLLED BY
DEFROST RELAY
OUTDOOR
FAN MOTOR
M5835
THERMOSTAT
HEAT 2
HEAT 1
DEFROST
RELAY
CONTACT
AUXILIARY
HEAT RELAY
L1
(HOT)
L2
TRANSFORMER