Honeywell EN2Z-0906GE51 R0708 Benutzerhandbuch

Seite von 160
USER GUIDE 
 ARENA/ RANGER
 
 
 89 
 
EN2Z-0906GE51 
R0708 
a. In Arena, select the remote ARENA you want to forward the alarms. 
b. In Destination name, enter a descriptive text for the ARENA. 
16. Click Advanced tab. 
Advanced
 Tab 
Behavior on Connection Failure 
 
 
 
a. In Retry count, enter the number of attempts ARENA should make to reach 
the remote ARENA. When ARENA still cannot reach the remote ARENA after 
retrying, it stops any further attempt until a new alarm comes in. 
b. In Retry interval (minutes), enter interval in minutes the ARENA waits 
between the retry attempts. 
17. Click the OK button. 
18. Continue with creating the trigger conditions as described in the “Create Trigger” 
section. 
 
Create Trigger 
A trigger is the condition (event) that causes ARENA to forward an alarm if the 
condition becomes true.  
 
Example: 
 
If the alarm severity (property) is critical (condition), any critical alarms will be 
forwarded. 
 
1.  Hover the cursor over the Configuration menu icon 
 and click Alarming 
in the configuration menu. 
2. Select 
the 
Forwarding
 tab and click Create new Trigger button, or select the 
Trigger 
tab and click Create Trigger button. The Trigger tab displays. Here you 
create the conditions for triggering the alarm forwarding by doing the following: