SPECIFICATIONS
Electrical Ratings:
Temperature Setting Range:
Heating: 40°F to 90°F (4.5°C to 32°C).
Cooling: 50°F to 99°F (10°C to 37°C).
Operating Ambient Temperature: 37°F to 102°F 
(2.8°C to 38.9°C).
Shipping Temperature: -30°F to 150°F 
(-34.4°C to 65.6°C).
Operating Relative Humidity (Non-condensing): 
5% to 90%.
Thermostat Dimensions: 3-7/16 in (86 mm) high x 
4-1/2 in. (114 mm) wide x 1-5/16 in. (33 mm) deep.
Heating equipment is 
running in the cool 
mode.
Heating equipment is not a heat pump 
but System Type (Installer Setup 
Number 1) is set to Heat Pump 
(Setting 1).
Set System Type (Installer Setup Number 1) 
to match the installed heating and/or cooling 
equipment.
Heating equipment does 
not turn off and the heat 
temperature setting is 
set below the room 
temperature (Heat On is 
not in the display).
Heating equipment is not a heat pump 
but System Type (Installer Setup 
Number 1) is set to Heat Pump 
(Setting 1).
Set System Type (Installer Setup Number 1) 
to match the installed heating and/or cooling 
equipment.
Cannot set the system 
setting to Heat.
System Type (Installer Setup Number 1) 
is set to Cool Only (Setting 4).
Set System Type (Installer Setup Number 1) 
to match the installed heating and/or cooling 
equipment.
System Setting Adjustment (Installer 
Setup Number 12) is set to Auto 
Changeover Only (Setting 2).
Set System Setting Adjustment (Installer 
Setup Number 12) to Manual Changeover 
(Setting 0) or Auto Changeover (Setting 1).
Cannot set the system 
setting to Cool.
System Type (Installer Setup Number 1) 
is set to Heat Only (Setting 2) or Heat 
Only with Fan (Setting 3).
Set System Type (Installer Setup Number 1) 
to match the installed heating and/or cooling 
equipment.
System Setting Adjustment (Installer 
Setup Number 12) is set to Auto 
Changeover Only (Setting 2).
Set System Setting Adjustment (Installer 
Setup Number 12) to Manual Changeover 
(Setting 0) or Auto Changeover (Setting 1).
Heat On is not in the 
display.
System setting is not set to Heat and/or 
the temperature setting is not set above 
the room temperature.
Set the system setting to Heat and set the 
temperature setting above the room 
temperature.
Cool On is not in the 
display.
System setting is not set to Cool and/or 
the temperature setting is not set below 
the room temperature.
Set the system setting to Cool and set the 
temperature setting below the room 
temperature.
Heat On is flashing in the 
display (Heat pumps 
only).
Compressor minimum off timer is active.
Wait up to five minutes for the heating 
equipment to turn on.
Cool On is flashing in the 
display.
Compressor minimum off timer is active.
Wait up to five minutes for the cooling 
equipment to turn on.
Table 5. Troubleshooting
Symptom
Possible Cause
Action
Terminal
Voltage 
(50/60 Hz)
Running Current
W Heating
20 - 30 Vac
.02 - 1.0A
W Heating 
(Powerpile)
750 mV dc
100 mA dc
Y Cooling
20 - 30 Vac
.02 - 1.0A
G Fan
20 - 30 Vac
.02 - .60A