T8400C, T8401C AND T8424C,D ELECTRONIC THERMOSTATS
68-0180-3
12
Table 3. Sequence of Operations.
a
In electric heat models, W and G are energized with calls for heat.
b
W1 and W2 terminals are energized in the T8424C,D models.
Fan Control
The FAN switch settings are On and Auto.
ON:The fan runs continuously.
AUTO:In cooling, the fan starts and stops 
with the cooling equipment. In heating, the 
fan starts a few minutes after the heating 
equipment turns on. When using an 
electric heat thermostat, the fan starts and 
stops with the heating equipment.
Heat Mode
With the SYSTEM switch at Heat, the thermostat controls the 
heating system. On a call for heat, the W terminal is energized 
and a flame is shown on the digital display.
Cool Mode
With the SYSTEM switch at Cool, the thermostat controls the 
cooling system. On a call for cool, the G and Y terminals are 
energized and a snowflake is shown on the digital display.
Minimum Off-Timer 
A minimum off-timer in the T8400C, T8401C and T8424C,D 
assures that the cooling compressor does not come on again 
for at least five minutes after it turns off. The minimum-off 
timer is triggered when the compressor turns off and when the 
system switch is changed. If the compressor turns off when 
the setpoint is changed, then the minimum-off timer is 
triggered. Power interruption and power restoration also 
trigger the minimum off-timer. The minimum-off timer operates 
only during the cooling cycle on the thermostat. 
CHECKOUT
Heating
1. Slide the system switch to Heat and the fan switch to 
Auto.
2. Press and hold the ▲ key to raise the temperature set-
ting several degrees above the room temperature. After 
approximately ten seconds the W terminal is energized 
and the heating equipment starts.
3. Press the ▼ key to lower the temperature setting below 
the room temperature. Heating equipment should stop.
Cooling
CAUTION
Low Temperature Hazard.
Operating at too low of an outdoor temperature 
can cause compressor damage.
Do not operate cooling if outdoor temperature is below 
50°F (10°C). Refer to manufacturer recommendations.
To avoid compressor damage, allow the compressor to 
remain off for five minutes before restarting.
1. Slide the system switch to Cool and the fan switch to 
Auto.
2. Press the ▼ key to lower the temperature setting sev-
eral degrees below the room temperature. After approx-
imately five minutes the G and Y terminals are 
energized and the cooling equipment starts.
3. Press the ▲ key to raise the temperature setting above 
the room temperature. Cooling system should shut 
down.
Fan
1. Slide the SYSTEM switch to Off and the FAN switch to 
On. The fan should run continuously.
2. Slide the FAN switch to Auto. In heating, the fan is con-
trolled directly by the heating equipment and may start a 
few minutes after the heating equipment turns on (on 
most systems). When using an electric heat thermostat, 
the fan starts and stops with the heating equipment. In 
cooling, the fan starts and stops with the cooling equip-
ment.
Make certain all equipment responds properly to the 
thermostat.
FAN Switch Settings
SYSTEM Switch Settings
Call for Action
Energize Terminals
Display Icons
Auto
Off
None
None
None
On
Any
Any
G
None
Auto
Cool
Cooling
G,Y
Auto
Heat
Heating
W
a,b