5) Additional Installation Information
5.1 Binding / Rebinding Procedure
The binding operation described below is required if:
•  Any of the system components (room thermostat or Relay Box) are replaced.
•  The Relay Box has incorrect or no binding data stored (e.g. when pre-bound system pack components
have been mismatched).
NOTE:
 During the binding procedure keep approximately 1m distance between the room thermostat and 
the Relay Box.
To bind/rebind:
1.
  Press and hold the Relay Box push button for 15 seconds to reset any previously stored data. After 15 
seconds the red LED will change to flashing 0.1sec on/0.9sec off. 
  NOTE: After 5 seconds the red LED will start to flash 0.5sec on/0.5sec off, but continue to hold the button).
2.
  Release the push button.
3. 
Press and hold the Relay Box push button for 5 seconds to enter the binding mode. The Red LED will 
start flashing at 0.5sec on/0.5sec off to confirm the binding mode has been entered.
4. 
Move the room thermostat slider to the OFF position and press the     and   buttons together along 
with the   button. The unit will display InSt and ‘CONTROL BINDING’.
5.
  Press the green   button to send the binding signal out to the Relay Box. The red LED is switched off to confirm 
successful binding operation. If the red LED still flashes push the button again until binding is successful.
6. 
Now go to Section 2) Installing the CM900 Wireless System to setup the system.
5.2 Multi-Zone System
Multiple  room  thermostats  and  Relay  Box  sets  can  also  be  used  to  control  multi-zone  systems  and  the 
CM927/921 room thermostat is compatible with a variety of other Honeywell products including HR80 radiator 
controllers (see below) and HCE80 underfloor heating controllers. If you intend to use it in this way additional 
installation and user instructions can be obtained by contacting the address at the end of this guide.
NOTE:
 Some of the labels supplied with the pack are for use in multi-zone applications.
5.3 Binding an HR80 Radiator Controller to the Room Thermostat
1.
  Press the bind button (1) for approximately one second and release. When the 
button  is  released,  the    symbol  flashes  and  the  software  version  number  is 
displayed for 30 seconds.
2.
  Move the room thermostat slider to the OFF position and press the     and   buttons 
together along with the   button. The unit will display InSt and ‘CONTROL BINDING’.
3.
  Press the green button to send the binding signal out to the radiator controller.
4.
  The radiator controller will display 
 once the signal has been received.
If several radiator controllers are to be controlled simultaneously in one room:
 
1.
  Press  the  bind  button  on  all  the  radiator  controllers  to  be  bound  to  the  room 
thermostat. The   symbol flashes continuously on the display of the radiator controller. 
2.
  Move the room thermostat slider to the OFF position and press the     and   buttons together along 
with the   button. The unit will display InSt and ‘CONTROL BINDING’.
3.
  Press the green   button to send the binding signal out to the radiator controllers. 
4.
  The radiator controllers will display 
 once the signal has been received. The set temperature at the 
radiator controller is automatically set to 20°C.
NOTE:
 The radiator controller can take up to 4 minutes to receive data from the room thermostat.