Honeywell T7350 Benutzerhandbuch

Seite von 40
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-2605—5
16
3. Press up S or down T until the desired time is 
displayed.
4. Press Run Schedule.
IMPORTANT
— Invalid holidays are ignored.
— Valid holidays require valid: month, day and duration.
— Holidays such as the fifth Tuesday of a month with 
only four Tuesdays are also invalid.
Copying a Day
Use the PDA or almost exclusively keys in the “Schedule” 
area of the keypad for this procedure:
1. Press Occupied.
2. Press Day to select the day to be copied.
3. Press Copy.
4. Press Copy again. The following day is automatically 
selected. (For example: If the day to be copied is Mon-
day, Tuesday will automatically be selected.)
5. If necessary, press Day until the day to receive the copy 
is displayed.
NOTE: To cancel the copy press Run Schedule before 
6. Press Copy.
NOTE: DONE displays for two seconds then the 
program display reappears.
7. Repeat steps through 6 for all the days desired.
8. Press Run Schedule.
Clearing Program Start Times
1. Press Occupied or Not Occupied until the start period to 
be cleared is displayed.
2. Press Day until desired day is displayed.
3. Press Clear Start Time.
4. Repeat steps 1 througfor all the start times to be 
cleared.
5. Press Run Schedule.
Temperature Setpoints
Setpoint Limits
The setpoint temperature range is 40°F to 90°F (4°C to 32°C) 
for heating and 45°F to 99°F (7°C to 37°C) for cooling.
NOTES: The ranges mentioned can be limited based upon 
setpoints and stops:
1.
The greater of the Minimum Heat Stop and the 
Not Occupied Heat setpoints determines the 
lowest setting to which the occupied heat setpoint 
can be adjusted: 
°F: Stop/NotOcc 
 OccHeat 
 (OccCool - 2).
°C: Stop/NotOcc 
 OccHeat 
 (OccCool - 1).
2.
The lesser of the Maximum Cool Stop and Not 
Occupied Cool setpoints determines the highest 
setting to which the occupied cool setpoint can be 
adjusted:
°F: Stop/NotOcc 
 OccCool 
 (OccHeat + 2).
°C: Stop/NotOcc 
 OccCool 
 (OccHeat + 1).
3.
The Maximum Occupied Heat Setpoint is limited 
by Occupied Cool Setpoint – 2° F (1° C).
4.
The Minimum Occupied Cool Setpoint is limited 
by the Occupied Heat Setpoint + 2° F (1° C).
Programming Temperature Setpoints
1. Press Occupied Heat.
2. Press up S or down T until the desired 
temperature is displayed.
3. Press Occupied Cool.
4. Press up S or down T until the desired 
temperature is displayed.
5. Press Not Occupied Heat.
6. Press up S or down T until the desired 
temperature is displayed.
7. Press Not Occupied Cool.
8. Press up S or down T until the desired 
temperature is displayed.
9. Press Run Schedule.
Temperature Setpoint Overrides
IMPORTANT
— The setup determines the duration of Occupied 
overrides.
— Default duration is three hours.
NOTE: To cancel the Override and immediately return to the 
program, press Run Schedule.
T7770 Setpoint Knob
A T7770 setpoint knob can remotely adjust the T7350 setpoint. 
Adjustment can be made with the sensor in override.
NOTES:
During override, only occupied and standby heat 
setpoints, and cool setpoints are adjusted.
The maximum adjustment is ±5° F (3° C).
With a disconnected or failed T7770, or a T7350 
not set for remote+setpoint, offset is zero.
T7771 Setpoint Button
A T7770 setpoint button can remotely adjust the T7350 
setpoint. Adjustment can be made with the sensor in override.
NOTES:
During override, only occupied and standby heat 
setpoints, and cool setpoints are adjusted.
The maximum adjustment is ±3° F (2° C).
With a disconnected or failed T7771, or a T7350 
not set for remote+setpoint, offset is zero.
Changing Temperature Setpoint Until Next Program 
Period
This is a simple change to perform even with the door closed:
1. Press up S or down T until the desired 
temperature is displayed.
NOTE: If done while in Standby or Not Occupied 
mode, Temporary Occupied override engages
2. The temporary temperature appears for approximately 
ten seconds, then the room temperature is displayed.