Honeywell T7350 Benutzerhandbuch

Seite von 40
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-2605—5
8
Wiring
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment 
circuitry.
Disconnect power supply before installation.
IMPORTANT
All wiring must comply with local electrical codes 
and ordinances.
NOTE: Maximum (and recommended) wire size is 
18-gauge (ø 1.02 mm). Do not use wire smaller than 
22-gauge (ø 0.644 mm).
Follow equipment manufacturer wiring instructions when 
available. Refer to the Wiring Diagram section for typical 
hookups. A letter code is located near each terminal for 
identification. Refer to Tables 3 through 8 for terminal 
designations.
1. Loosen subbase terminal screws and connect system 
wires.
2. Securely tighten each terminal screw. 
3. Push excess wire back into the hole in the wall.
4. Plug the hole with nonflammable insulation to prevent 
drafts from affecting the thermostat.
Table 3. T7350A Subbase for Single-stage Heat, 
Single-stage Cool Systems.
a
Factory jumper between RC and RH for systems with one 
transformer.
b
For changeover functional details, see Operation section.
Table 4. T7350B Subbase for Two-stage Heat, 
Two-stage Cool Systems.
a
Factory jumper between RC and RH for systems with one 
transformer.
b
For changeover functional details, see Operation section.
Terminal
Description
Co
nv
en
tio
n
al
H
eat Pump
RC
a
RC
a
24 VAC Cooling transformer.
RH
a
RH
a
24 VAC Heating transformer.
X
X
Common.
G
G
Fan  relay.
aux aux Conventional: Auxiliary relay or 2nd Stage of 
heating or cooling relay.
Heat Pump: Auxiliary relay or 1st Stage auxiliary 
heat relay.
W1 O/B Conventional: Stage 1 heating relay.
Heat Pump: Changeover relay for heating (B) or 
cooling (O)
b
.
Y1
Y1
Conventional: Stage 1 cooling relay.
Heat Pump: Stage 1 compressor relay.
Terminal
Description
Conve
n
tional
Hea
t Pump
RC
a
RC
a
24 VAC Cooling transformer.
RH
a
RH
a
24 VAC Heating transformer.
X
X
Common.
aux aux Conventional: Auxiliary relay or 3rd stage of 
heating or cooling.
Heat Pump: Auxiliary relay or 2nd stage auxiliary.
W1 O/B Conventional: Stage 1 heating relay.
Heat Pump: Changeover relay for heating (B) or 
cooling (O)
b
.
W2 W1 Conventional: Stage 2 heating relay.
Heat Pump: 1st Stage auxiliary heat relay.
Y1
Y1
Conventional: Stage 1 cooling relay.
Heat Pump: Stage 1 compressor relay.
Y2
Y2
Conventional: Stage 2 cooling relay.
Heat Pump: Stage 2 compressor relay.
AS AS Discharge Air Sensor connection (1).
AS AS Discharge Air Sensor connection (2).
OS OS Outdoor Air Sensor connection (1).
OS OS Outdoor Air Sensor connection (2).
G
G
Fan  relay.
T3
T3
T7770 Remote Sensor connection (3).
T4
T4
T7770 Remote Sensor connection (4).
T5
T5
T7770 Remote Sensor connection (5).
T6
T6
T7770 Remote Sensor connection (6).
T7
T7
T7770 Remote Sensor connection (7).