DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install and Wire Telephones and Other Equipment 
Page 5-113
Add Packet Bus to R6si 
5
Add Packet Bus to R6si
Standard Reliability R6si System
Disable Alarm Origination
1. Enter change system-parameters maintenance and press 
Enter
2. Set the 
Alarm Origination Activated
 field to n.
!
CAUTION:
If you do not disable Alarm Origination, the system may generate 
alarms, resulting in unnecessary trouble tickets. 
3. For some releases of software, disable
 Cleared Alarm 
Notification 
and 
Restart Notification
 before submitting the 
form.
Save Translations
1. If the system is high or critical reliability, enter status system 1 and press 
Enter
 to verify that the system is in the “active/standby” mode.
2. Enter save translation and press 
Enter
. This instructs the system to take all 
translation information in memory and write it to the translation card or 
tape.
Install Circuit Packs
1. Power down the PPN, then EPN1, and then EPN2 as required.
2. At the PPN, install the appropriate circuit packs. See 
Table 5-20
.
1.
Quantity of this pack should equal the number of EPNs.
2.
Optional for digital trunk testing.
Table 5-20.
Circuit Pack Locations for Packet Bus in R5si+m PPN
Circuit Pack
Carrier
Quantity
Slot
TN778
Control Carrier A
1
PACKET CONT
TN570
Control Carrier A
1 or 2
1
EXPN INTFC/1 and /2
TN771C
Control Carrier A
1
2
Any Available Port Slot