1.  Turn off the gas supply. (if connected)
2.  Open the roof and remove the door.
3.  Remove the battery. (if installed)
4.  Remove the engine air in baffle located on the left-
hand  side  of  the  battery  compartment.  Two  M6 
screws  are  located  on  top  of  the  baffle  and  two 
M6 screws are located on the inside of the baffle 
towards the back.
5.  Remove the small hose clamp and hose from the 
fuel regulator. It may be necessary to pry the hose 
off of the brass fitting using a screwdriver to gen-
tly lift up the hose edge.
6.  Remove  the  small  brass  hose  fitting  from  the 
regulator casting.
7.  Place the small fuel jet, thread side first, into the 
threaded  hole  originally  occupied  by  the  brass 
hose fitting (Figure 1.4).
Figure 1.4 - Demand Regulator
BRASS HOSE
FITTING
IDLE CIRCUIT
PORT
U
1
T
TAP
1/8 NPT
BRASS HOSE
FITTING
FUEL HOSE
SMALL
FUEL JET
REGULATOR
HOUSING PORT
ADJUSTER
SCREWS
OUTLET PORTS
8.  Using a short No. 2 Phillips screw driver, thread 
the  small  fuel  jet  into  the  regulator  casting.  Do 
not over tighten.
9.  Apply  thread  sealant  to  the  threads  of  the  hose 
fitting and replace it into the regulator body.
10. Re-attach  the  small  hose  and  hose  clamp  and 
tighten as necessary.
11. Replace the engine air in baffle using the four M6 
screws.
12. Identify  both  brass  adjustment  screws  on  the 
regulator.
NOTE:
One  adjustment  screw  can  be  accessed  from  the 
front of the unit and the second can be accessed 
from the back of the unit enclosure by removing 
the  plastic  hole  plug.  The  screw  can  be  turned 
with a long flat blade screwdriver.
13. To  adjust  the  system  to  run  on  LP  fuel,  turn 
BOTH  adjuster  screws  1/2  TURN  CLOCKWISE. 
The  system  should  now  be  set  for  maximum 
power  and  best  perfomance. 
DO  NOT,  UNDER 
ANY  CIRCUMSTANCES,  REMOVE  THE  SET 
PINS  FROM  THE  REGULATOR  HOUSING. 
THIS WILL VOID THE WARRANTY.
14. It may be necessary to make minor adjustments 
to the preset adjustment screw settings to achieve 
maximum power, particularly at higher altitudes. 
If experiencing problems with the unit producing 
maximum power, follow the procedure in Section 
2.6 (Adjusting the Fuel Regulator).
1.9  LOCATION
1.9.1  GENERATOR
Install the generator set, in its protective enclosure, 
outdoors, where adequate cooling and ventilating air 
is always available. Consider these factors:
•  Install  the  unit  where  air  inlet  and  outlet  open-
ings  will  not  become  obstructed  by  leaves,  grass, 
snow, etc. If prevailing winds will cause blowing or 
drifting, consider using a windbreak to protect the 
unit.
•  Install  the  generator  on  high  ground  where  water 
levels will not rise and endanger it.
•  Allow sufficient room on all sides of the generator 
for  maintenance  and  servicing.  A  good  rule  is  to 
allow three feet of space on all sides.
•  Where  strong  prevailing  winds  blow  from  one 
direction,  face  the  generator  air  inlet  openings  to 
the prevailing winds.
•  Install the generator as close as possible to the fuel 
supply, to reduce the length of piping.
•  Install  the  generator  as  close  as  possible  to 
the  transfer  switch.  HOWEVER,  REMEMBER 
THAT  LAWS  OR  CODES  MAY  REGULATE  THE 
DISTANCE.
1.9.2  TRANSFER SWITCH
1.9.2.1   7 kW, 12 kW and 15 kW Units
Transfer  switches  for  use  with  these  generators 
are  sold  separately  and  can  be  purchased  from 
Authorized Dealers.
•  Install  the  transfer  switch  on  a  firm,  sturdy  sup-
porting structure.
•  To  prevent  switch  distortion,  level  the  switch  if 
necessary.  This  can  be  done  by  placing  washers 
between  the  switch  enclosure  and  mounting  sur-
face.
•  Never install the switch where water or any corro-
sive substance might drip onto the enclosure.
•  Protect  the  switch  at  all  times  against  excessive 
moisture, dust, dirt, lint, construction grit and cor-
rosive vapors.
•  Failure to utilize the manufacturer’s transfer switch 
with this generator may void the warranty.
Section 1 — General Information
Air-cooled 7 kW, 12 kW and 15 kW Generators
  8