Parallel Compressor Systems Installation & Operations Manual, October 2004  
3
Parallel Compressor Systems
Introduction
Parallel Compressor systems are central refrigeration units 
employing 2 to 8 parallel piped compressors, a control panel, 
and receiver mounted on one common base frame. The system 
may be designed for either Indoor or Outdoor use. The Outdoor 
design may include the condenser mounted and piped.  
The selection and design of the system is based on the needs 
of  the  individual  customer. The  most  important  point  in 
planning an installation of the Heatcraft parallel system is the 
proper selection of the system components for the particular 
application.  
Component parts have been selected for their dependability 
and  availability  to  keep  service  problems  to  a  minimum.  
Simplicity  of  design  has  also  made  the  Heatcraft  parallel 
system one of the easiest to service and install. The simplicity 
and compactness of the Heatcraft design make the addition of 
hot gas defrost and/or heat reclaim a simple and economical 
feature.
In the following pages will be found explanations of system 
components, wiring and piping diagrams, control settings, and 
operational guides.  
Inspection
Unit inspection should be assigned to a dependable individual.  
Inspect the parallel system and any accessories shipped with 
them for damages or shortages before and during unloading.  
All items on bill of lading should be accounted for prior to 
signing the shipping receipt. Note any shortages or damage on 
carrier’s delivery receipt (Specify the extent and type of damage 
found).  Unit  should  be  inspected  carefully  for  concealed 
damage.  Notify  the  Heatcraft  sales  representative  and  the 
carrier of the damage immediately. Request an immediate 
joint inspection with the carrier (Do not repair the unit until 
inspected by carrier’s representative). Care should be exercised 
when uncrating units to prevent damage.   
The system is shipped with a holding charge of dry nitrogen.  
Check to see that pressure is still in the unit upon receipt.  
Report lack of pressure immediately to the Heatcraft service 
department.
NOTE:  Accessory items such as drier cores, 
mounting pads, modems, etc. may be 
packaged in a separate carton. Be sure 
that you receive all items.
Unit Designation
Units are identified by letter, brand, compressor type, quantity 
of compressors, horsepower, condenser type, control voltage, 
defrost type, refrigerant/range, unit voltage and application.  
Unless otherwise requested by the customer all refrigeration 
circuits are numbered from one to the highest and from left to 
right while facing the electrical panel.
Model Definition:
1st digit - Brand (B, C, H, or L)
2nd digit - Compressor Type
 
H - Hermetic
 
R - Reciprocating
 
S - Screw
 
O - Open
 
Z - Scroll
®
 
C - Compound
3rd digit - Unit Construction
 
R - Remote Condenser
 
U - Attached Condenser
 
H - Hybrid
 
M - Multi-compressor Platform
 
F - Frame Hybrid (Frame + Standard Unit)
4th digit - Compressor Quantity
 
2 - 2 Compressors
 
3 - 3 Compressors
 
4 - 4 Compressors
 
Etc.
5th, 6th, & 7th digit - Horsepower
 
030 - 30 HP
 
075 - 75 HP
 
100 - 100 HP
 
Etc.
8th digit - Condenser Type
 
A - Air
 
W - Water
 
E - Evaporative
9th digit - Control Voltage
 
A - 115/1/60
 
B - 208-230/1/60
 
C - 24/1/60
10th digit - Defrost Type
 
A - Air/Off-Cycle
 
E - Electric
 
G - Hot Gas
 
M - Multiple
 
W - Water
11th digit - Temperature Range
 
L  - Low
 
M - Medium
 
H - High
 
C - Combination
 
X - Ultra Low
12th digit - Refrigerant Type
 
2 - R-22
 
4 - R-134A
 
6 - R-404A, R-507
 
8 - Multiple
13th digit - Unit Voltage
 
C - 208-230/3/60
 
D - 460/3/60
 
E - 575/3/60
 
J - 208/3/60
 
K - 230/3/60
 
M - 380/3/60
14th digit - Application
 
1 - Indoor
 
2 - Outdoor