Toshiba E6581830 Benutzerhandbuch
E658130
- 42 -
6.6.
Program example for parameter writing
Example 6 shows
a ladder logic to
chang the setting of f311 of station 1 inverter to 1
f311
: Reverse-run prohibition reading code number: 2311H (hexadecimal)
Reverse-run prohibition set data: 1 (decimal)
X0
X0F X1
SW80.0
M0
X20
M300
M301
X100F
[ MOV H2311 W102]
M302
X100F
[ MOV W2 D2]
( M0)
[ PLS M300]
[ SET M301]
[ MOV K1 W103]
[ SET Y100F]
[ RST M301]
[ SET M302]
[ RST Y100F]
[ RST M302]
[ END]
Check the ready of the Station 1
Write f311 write code (2311H) to
RWw2 and r
RWw2 and r
everse-run prohibition
setting
Turn on the instruction code
execution
execution
Read reply code (RWr2) to D2 when the
Instruction code execution completion
flag
Instruction code execution completion
flag
Turn off the instruction code
execution
execution
Example