Mitsubishi Electronics 882.00273.00 Benutzerhandbuch

Seite von 101
7-5  Mitsubishi Communications Manual 
The Mitsubishi blender uses a FX-2N processor that communicates with the outside world using 
MELSEC FX protocol over Ethernet hardware.  It’s Ethernet speed is 10 Mbits/second.  The blender must 
be purchased from ACS with the Ethernet option.  If this was not done at the time of purchase it can be 
added afterwards by consulting the factory.  The blender has a programmable IP address and subnet mask 
that can be programmed from software that is provided by DIGI for the Ethernet module (refer to their 
manual). 
Ethernet is the standard that we support, but Mitsubishi also supports Profibus and MELSEC Serial 
communications.  Refer to Mitsubishi for parts and information. 
The communications port settings on the PLC are: 19,200 baud; 8 data bits; no parity;1 stop bit; software 
flow control. 
The communications must also be enabled.  From the main screen touch the  “next” button to go to the 
“inventory” page.  Touch “Log in” and type in “5413”.  Then touch the “ACS logo” and this will take you 
to setup.  Touch the “Network Setup” button and ensure that communications is enabled.  If it wasn’t then 
you’ll need to change it and then reboot the PLC for it to take effect.  The Ethernet module takes about 45 
seconds to regain communications upon boot. 
Below are the items that can be accessed for the blender: 
Note:   ITEMS MARKED (R) ARE READ ONLY AND ITEMS MARKED 
(RW) ARE READ/WRITE 
GENERAL BLENDER INFO 
1 (R) plc_version,D1942,SHORT VALUE (xx.x) 
2 (R) number_of_hoppers,D1702,SHORT VALUE (number of hoppers on the blender) 
3 (R) maximum_blender_throughput,D1056,LONG VALUE(maximum rate blender can achieve) 
4 (R) average_batch_time, D1938,SHORT VALUE (average amount of time it takes to finish the batch) 
5 (R) average_process_rate,D1334,LONG VALUE (average rate at which the process is consuming 
blended material) 
BLENDER STARTING AND STOPPING 
1 (R) blender_started,M500 
2 (RW) blender_start_request,M540 (toggle this to start or stop the blender,  blender will switch it’s 
current status, you must also reset this bit after completion) 
3 (RW) abort_batch_request,M508 (toggle this to immediately stop the blender even if the batch is 
incomplete, you must also reset this bit after completion) 
BF1-615.3 
Chapter 7: 6BAppendix 
94 of 101