Samsung SSA-P102 Benutzerhandbuch

Seite von 24
22_
 
troubleshooting
troubleshooting
The reader reads a card normally but no 
reaction is made to SSA-P102 or an 
irrelevant card number is displayed.
1) 
 Check the power source of the reader.
(Check if the LED indicator of the reader is blinking when it has read a card.)
2) 
 Check if the reader works properly.
(Disconnect the reader from the system and use a measuring device such as an oscilloscope 
to measure the output port of the reader.)
3) 
Check if the reader is properly connected to the system.
-  Check if the Wiegand communication lines between the reader and the system are 
properly established. (D0, D1)   
- The Wiegand communication line should be connected to GND. 
(A different power source may be fi ne but the earth-grounding point should be 
connected to GND of the device.)
4) 
 If you fi nd the output signal from SSA-P102 but with severe noise when using a measuring 
device to measure the Wiegand communication line, please check the followings:
- Connect the shield wire and the spare wire of the cable to GND.
- Use the repeater.
5) 
 If the problem persists after you followed the instructions above, please contact the 
customer service for technical assistance.
No communication is available when the 
system is in sync with the PC.
1) 
 Check the communication settings between the PC application and the device.
       -  Check the board ID (COMM address) and match it with that of the PC application.
       -  Specify a unique board ID (COMM address) for each of the multiple devices.
       -  Check the baud rate if it matches with the PC application.
       -  Check if the communication port of the PC matches that of the PC application.
       - Check the communication settings of the PC application.
          Parity Bit : NONE, Data Bit: 8bit, Stop Bit: 1bit
2)  Check the connection staus of RS-232 and RS-422.
RS-232
RS-422 (Independent Communication)
SSA-P102
PC
SSA-P102
RS-232/422
Converter
PC
TX Port
RX
RX(-)
TX(-)
Connected to the 
RS-232 cable of the 
converter
RX Port
TX
RX(+)
TX(+)
GND
GND
TX(-)
RX(-)
TX(+)
RX(+)
RS-422(Multi-Unit Communication)
SSA-P102
SSA-P102
RS-232/RS-422
PC
RX(-)
RX(-)
TX(-)
Connected to the 
RS-232 cable of the 
converter
RX(+)
RX(+)
TX(+)
TX(-)
TX(-)
RX(-)
TX(+)
TX(+)
RX(+)
For RS-422 communications, install a termination resistor at the point where the 
system is connected to the RS-422/RS-232 converter of the PC.
(Install a 120Ω termination resistor between the RX+ and the RX- terminals on the 
device side, another 120Ω between the TX+ and the TX- terminals; the same should 
be done to the converter. If you are not sure about the wiring, contact the customer 
service for your help.) 
If the problem persists after you followed the instructions above, this may be caused 
by the defective of an internal circuit. Contact the customer service.
¼    If no communication is established after you tried to do so with multiple 
devices, pick just one device and connect it to the RS-232/RS-422 converter, 
and to the PC. Then, check if there is any communication available.