Setting the option switches & function keys
Setting the outdoor unit KEY
K1 K2 K3 K4
SW01
SW02 SW03
Test mode
Display mode
Reset
Option
ON
OFF
Setting by model name
AP80S0✴X
AP0AS0✴X
Setting model (Heat pump/Cooling only)
Heat pump
Cooling only
❋
DIP SW01 is a factory default setting. Do not change the setting on your own.
❋
When installation is completed, check the status of functional setting on each model before the trial operation.
K2 (Number of pressing)
KEY operation
7-Segment display
1
Cooling test operation
2
End KEY operation
No display
K3 (Number of pressing)
KEY operation
7-Segment display
1
Reset operation
Same as reset status
K4 (Number of
pressing)
Displayed contents
Display
SEG 1
SEG 2
SEG 3
SEG 4
1
Discharge temperature
1
(Data) 87°C (Display) 0, 8, 7
2
Outdoor temperature
2
(Data) -12°C (Display) -, 1, 2
3
-
-
-
4
Evap. Temperature
4
(Data) 15°C (Display) 0, 1, 5
5
Indoor temperature
5
(Data) 27°C (Display) 0, 2, 7
6
-
-
-
7
Operation data display
7
Heat pump
Protection control
Compressor
0: Cooling
1: Heating
1: Heating
0: No protection
control
1: Frozen
2: Overload
3: Discharge
2: Overload
3: Discharge
0: Stop
1: Minimum operation
1: Minimum operation
(1 Comp)
2: Rated operation (2
Comp)