Setting the option switches & function keys
Setting the outdoor unit KEY
K1 K2 K3 K4
SW01
SW02 SW03
Test mode
Display mode
Reset
Option
ON
OFF
Setting by model name
AP80S0✴X
AP0AS0✴X
Setting model (Heat pump/Cooling only)
Heat pump
Cooling only
 
DIP SW01 is a factory default setting. Do not change the setting on your own.
 
When installation is completed, check the status of functional setting on each model before the trial operation.
K2 (Number of pressing)
KEY operation
7-Segment display
1
Cooling test operation
2
End KEY operation
No display
K3 (Number of pressing)
KEY operation
7-Segment display
1
Reset operation
Same as reset status
K4 (Number of 
pressing)
Displayed contents
Display
SEG 1
SEG 2
SEG 3
SEG 4
1
Discharge temperature 
1
(Data) 87°C  (Display) 0, 8, 7
2
Outdoor temperature
2
(Data) -12°C  (Display) -, 1, 2
3
-
-
-
4
Evap. Temperature
4
(Data) 15°C  (Display) 0, 1, 5
5
Indoor temperature
5
(Data) 27°C  (Display) 0, 2, 7
6
-
-
-
7
Operation data display
7
Heat pump
Protection control
Compressor
0: Cooling
1: Heating
0:  No protection 
control
1: Frozen
2: Overload
3: Discharge
0: Stop
1:  Minimum operation 
(1 Comp)
2:  Rated operation (2 
Comp)