   Items to prepare   
(compressor and insulation tape should be prepared by an installation technician.)
1.  As shown in the figure, peel off the shields from the  rubber/wire  
of the power cable.  
-  Peel off 20 mm of the wire shields of the tube installed already.
2.  Insert both sides of core wire of the power cable into the connection sleeve.
3.  Using a compressor, compress the two points and flip it over  
 and compress another two points in the same location.
 
-  The compression dimension should be 8.0.
 
-  After compressing it, pull both sides of the wire to  
 make sure it is firmly pressed.
4.  Wrap it with the insulation tape twice or more and position your contraction 
tube in the middle of the insulation tape. A total of three or more layers of 
insulation is required.
5.  Apply heat to the contraction tube to contract it.
6.  After tube contraction work is completed, wrap it with the 
 insulation tape to finish.
 
-  Make sure that the connection parts are not exposed to outside.
 
-  Be sure to use insulation tape and a contraction tube made of approved 
reinforced insulating materials that have the same level of withstand voltage 
with the power cable. (Comply with the local regulations on extensions.)
How to connect your extended power cables
Tools
Crimping plier
Connection sleeve (mm)
Insulation tape
Contraction tube (mm)
Spec
MH-14
20xØ7.0(HxOD)
Width 18mm
50xØ8.0(LxOD)
Shape
40mm
Insulation tape
Contraction tube
(Unit: mm)
120
60
20
20
20
180
Power cable (provided by us)
20
Wire tube power cable
Connection sleeve
Comp. dim.
Compress it 4 times
5mm
Insulation tape
•  For information about the power cable specifications for indoor and
outdoor units, refer to the installation manual.
•   After peeling off the tube wire, you must insert a contraction tube.
•   In case of extending the electric wire, please DO NOT use a round-shaped pressing socket. 
-  Incomplete wire connections can cause electric shock or a fire.
Junfrau EE_AR09FSFK@_IB&IM_DB68-06190A-00_EN.indd   48