APC galaxy 9000 Benutzerhandbuch

Seite von 40
34006451EN/AC
 - Page 4
1. Characteristics
 
1.1 Characteristics common to all cubicles
MGE
TM 
Galaxy
TM
 9000 UPS: example of a rectifier-inverter cubicle
After moving them to their installation location on their pallets, MGE
TM 
Galaxy
TM
 9000 cubicles can be moved short distances using a forklift or 
pallet-mover when the front, rear and side base panels are not mounted. The forks can be inserted from all four sides into 100 mm ±10 mm 
high openings;
the unadjusted cubicle height (H) is 1900/2000 mm; after lifting the cubicle, the height can be adjusted ±10 mm by screwing in or out the four 
feet;
the bearing surface corresponds to the area of the four cylindrical foot pads (60 mm diameter) positioned in each corner 
of the cubicle;
the cubicle depth (D) is 840 mm (800 mm without doors and panels);
operating temperature range for rectifier-inverter, frequency converter or Static Switch Cubicles: 0 °C to 35 °C at rated output (40 °C for a 
maximum of 8 hours) and 30 °C maximum for overload conditions. Operation outside the specified temperature range will reduce service life;
relative humidity: 95 % maximum;
maximum operating altitude without derating: 1000 m;
connection via the bottom for rectifier-inverter cubicles, or via the top with the addtion of an optional duct that can be installed on the right side 
of the cubicle. The auxiliary and Static Switch Cubicles are designed for connections via the top 
or bottom.
the connection cables may be run in three ways:
in a trench running under the cubicles, 
under a false floor,
on the floor under the cubicles, in the free space equal to the height of the feet; in this case the cables should be run side by side to avoid 
blocking the flow of air for ventilation.
the intercubicle connection cables are not supplied (except for the wires for auxiliary interconnections);
normally the cubicles do not have to be secured to the floor; the footpads nevertheless have holes with an average depth of 12 mm designed 
for the fitting of M16 anchor bolts;
the cubicle doors are secured by Ronis locks (key 405).
H
L
P
Galaxy 6000
w
w
w
.
m
g
e
u
p
s
.
c
o
m
GALAXY
 6000   40
0 kVA
SALLE
 IQ
Load p
rotecte
d
125 kV
A
120%
100%
50%
80%
0
0 Hour
 50 Min
.
100%
50%
0
Availa
ble Ba
ckup Ti
me
Load l
evel
Norma
l AC
Bypas
s AC
Load
equipm
ent
Q1
Q5N
QF1
Q4S
Q3BP
15:24:
32   30
/05/2005
Home
Alarms
Online
Trend
Statist
ics
Rectifie
r
Batter
y
Inverter
Bypas
s
Outpu
t
Set up
Galaxy
 6000
w
w
w
.
m
g
e
u
p
s
.
c
o
m
GALAX
Y 6000  
 400 kV
A
SALLE
 IQ
Load p
rotecte
d
125 kVA120%
100%
50%
80%
0
0 Hour 5
0 Min.
100%
50%
0
Availa
ble Ba
ckup Ti
me
Load l
evel
Normal AC
Bypass
 AC
Load
equipme
nt
Q1
Q5N
QF1
Q4S
Q3BP
15:24:
32   30/
05/2005
Home
Alarms
Online
Trend
Statist
ics
Rectifi
er
Battery
Inverte
r
Bypas
s
Output
Set up