PIR APPLICATION GUIDE FOR TB7200 AND TB7300 SERIES THERMOSTATS
63-4526—01
2
OCCUPANCY SENSOR COVER MODELS 
OCCUPANCY SENSING CONFIGURATION PARAMETERS
The following configuration parameters are specifically provided as standard on all TB7200 and TB7300 Series thermostats. 
They are associated with the advanced occupancy functionality introduced with the addition of a PIR cover or a remote PIR 
sensor. These parameters will allow the installer to set the thermostat occupancy functions exactly as required by the application.
Their functionality only becomes active if a PIR occupancy sensor cover is connected or one of the binary/digital input is 
configured to use a remote PIR sensing device.
PIR Cover OS Number
Description
Compatible with the 
Following Thermostats
TB-PIR-FCU-C
PIR cover with Commercial FCU interface
TB73x0X5014(X)
TB-PIR-FCU-L
PIR cover with Hotel/Lodging interface
TB73x5X5014(X)
TB-PIR-ZN 
PIR cover for zoning thermostats
All TB7200 Series
Configuration Parameter
Description of Configuration parameter
BI or DI input door setting
Default: None for no function used
It is possible to configure some of the digital or binary inputs to effectively use the 
advanced functions allowed by the installation of a door switch contact. This function is 
mostly used with fan coil units in lodging applications
When a door contact is used and configured, the Stand-By timer is no longer active. 
The occupancy toggle between occupied and stand-by is now dictated by both the door 
contact and the PIR cover.
• Movement detected by the PIR cover = Always occupied
• Door opens / closes detected by the door switch = Stand-by mode
Stand-by Heating Setpoint:
Default: 69 °F (20.5 °C)
This parameter sets the stand-by heating setpoint value. 
The set value of this parameter should reside between the occupied and unoccupied 
heating setpoints and make sure that the difference between the stand-by and occupied 
value can be recovered in a timely fashion when movement is detected in the zone. 
Adjustable from 40 to 90 °F ( 4.5 to 32 °C ) in 0.5 degree increments.
Stand-by Cooling Setpoint:
Default: 78 °F (25.5 °C)
This parameter sets the stand-by cooling setpoint value. 
The set value of this parameter should reside between the occupied and unoccupied 
cooling setpoints and make sure that the difference between the stand-by and occupied 
value can be recovered in a timely fashion when movement is detected in the zone. 
Adjustable from 54 to 100 °F ( 12.2 to 37.8 °C ) in 0.5 degree increments.
Stand-by Time:
Default 0.5 hours
This parameter sets the time delay between the moment where the PIR cover detected 
the last movement in the area and the time which the thermostat stand-by mode and 
setpoints become active. 
Adjustable from 0.5 to 24 hours in .5hr increments
Unoccupied Time:
Default 0.0 hours
If no movement is detected in the area and the current mode is stand-by, this parameter 
will then set the time delay between the moment where the thermostat toggles to stand-
by mode and the time which the thermostat unoccupied mode and setpoints become 
active. 
The factory value or 0.0 hours: Setting this parameter to its default value of 0.0 hours 
disables the unoccupied timer. This prevents the thermostat from drifting from stand-by 
mode to unoccupied mode when PIR functions are used
Adjustable from 0.0 to 24 hours in .5hr increments