Do not mount the subbase where it may be affected by: 
— drafts or dead spots behind doors or in corners. 
— hot or cold air from ducts. 
— radiant heat from the sun, fireplaces, or appliances. 
— concealed pipes and chimneys. 
— unheated (uncooled) areas such as an outside wall. 
CAUTION 
•   Disconnect power supply to prevent electri­
cal shock or equipment damage. 
•   Do not short across coil terminals on relay, 
this can burn out the thermostat heat 
anticipator. 
•   Do not overtighten captive mounting screws 
because damage to subbase threads can result. 
MOUNTING AND WIRING 
Disconnect power supply before beginning installation to 
prevent electrical shock or equipment damage. 
All wiring must comply with local codes and ordinances. 
1.  In replacement applications, check the existing sub­
base wires for cracked or frayed insulation. Replace any 
wires in poor condition. If the wire is plastered into the wall, 
make a hole next to the wires and loosen the wires so that the 
wires can be pushed back into the wall later. 
2.  In new installations, run wiring (if necessary) to the 
subbase location. 
IMPORTANT: To prevent interference with the thermostat 
linkage, keep wire length to a minimum and run wires 
as close as possible to the subbase. 
3.  Connect the wires to the terminals inside the subbase. 
Refer to equipment manufacturer instructions for Q539 
wiring diagrams. If not available, refer to Fig. 1 through 5. 
4.  Push excess wire back through the hole and plug any 
opening with insulation to prevent drafts that can affect 
performance. 
5.  Loosely fasten the thermostat subbase to the wall with 
a screw through the left mounting hole. Adjust the subbase so 
it is approximately level and start the second screw through 
the right mounting slot. Do not tighten. 
6.  Level the thermostat subbase using a spirit level as 
shown in Fig. 1. 
7.  Tighten mounting screws. 
IMPORTANT: An incorrectly leveled subbase will cause 
the temperature control to deviate from setpoint. 
8.  Mount and wire the thermostat to the thermostat sub­
base using the equipment manufacturer’s instructions. 
Fig. 1—Level Q539 using a spirit level . 
SPIRIT 
LEVEL 
LEVELING 
POSTS (2) 
MOUNTING 
SLOTS 
M3319A 
OPENING FOR 
THERMOSTAT 
WIRING 
Fig. 2—Barrier configuration. 
FOR STRAIGHT 
INSERTION– 
STRIP 5/16 in. (8 mm) 
FOR WRAPAROUND– 
STRIP 7/16 in. (11 mm) 
SUBBASE TERMINAL SCREW 
M8831 
BARRIER 
Fig. 3—Typical hookup for Q539A in heating­
cooling application with remote lockout 
indication. 
Q539A/T87F INTERNAL SCHEMATIC 
T87F 
TEMP. 
FALL
R1 
ADJUST-
ABLE 
HEAT 
ANTICIPATOR 
FIXED COOL
ANTICIPATOR 
LOCKOUT 
INDICATOR 
LIGHT 
HEAT 
OFF 
COOL  HEAT  OFF  COOL 
AUTO 
FAN 
ON 
X
 RH
 
W
  Y
 
G
 
RC
 
SWITCH 
HEATING 
CONTROL 
COOLING 
CONTROL 
FAN 
RELAY 
HEATING 
TRANSFORMER 
COOLING 
TRANSFORMER 
L1
L1 
W1 
Y1 
L2  
L2 
(HOT) 
(HOT) 
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED. 
M8832 
95-6486—9