Table 3.  Heat Cycle Rate.
NOTE:
The cooling cycle rate does not require adjustment and therefore cannot be changed.
Fahrenheit/Celsius Indication
Use DIP switch 3 to set the desired temperature indication. See Table 4.
Table 4. Temperature Indication.
STEP 9. MOUNT THE THERMOSTAT
Heating System
Cycles Per Hour DIP Switch 1 DIP Switch 2
Steam, Gravity
1
On
On
High Efficiency Warm Air (90%+ efficiency), Hot Water, Heat Pump 3
Off
On
Gas or Oil Warm Air (factory setting)
6
Off
Off
Electric Warm Air
9
On
Off
In Floor Radiant Heat
Check with manufacturer for recommended 
cycle rate.
Fahrenheit/Celsius Display
DIP Switch 3
Fahrenheit (factory setting)
Off
Celsius
On
M19498
ENGAGE TABS 
AT BOTTOM OF 
THERMOSTAT 
AND WALL PLATE.
PRESS UPPER
EDGE OF CASE
TO LATCH