Set Up and Calibration Procedures 
Input Set Up Group 
Revision 7 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
39 
7/08  
 
 
Input Set Up Group 
Table 10 lists the parameters and selections available when the SET INPUT group is selected.   
On the keypad and local display: 
•  Press the SET UP key to enter the Input Set Up group.   
•  Press the FUNCTION key to scroll through the prompts listed in the set up group.   
•  Press the
or 
 keys to view selections or change range settings.   
Table 10 Input Set Up Group Parameters 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink Prompt 
 
IN TYP 
Note: I
f input 
type from model 
selection guide 
is:               
0/4-20mA, 0/1-
5Vdc, 0-10Vdc  
 
 
 
 
 
 
4-20 
0-20 
1-5V 
0-5V  
0-10  
R_SP              
INPUT ACTUATION TYPE
— This selection specifies the 
signal type and range you are going to use for the actuator 
input. Be sure that the values configured for the high and low 
range, alarm setpoint, etc. are within the measuring range 
for the selected signal range. 
4 to 20 mA 
0 to 20 mA 
1 to 5 Volts dc 
0 to 5 Volts dc 
0 to 10 Volts dc 
  
Remote Setpoint 
(via communications)                           
NOTE:  Changing the Input Actuation Type will restore the 
actuator calibration to its factory values.  
IN TYP 
 
S_90 
Series 90 – 
0 to 135 ohms. 
Note: If input type from model selection guide is:  Series 90 
control 
INP HI 
10.0 to 100 
default = 100 
INPUT HIGH RANGE VALUE
 in % is displayed. 
NOTE:  When Input Type (R_SP or S_90) is selected, Input 
Hi is not configurable. 
INP LO 
0.0 to 90.0 
default = 0.0 
INPUT LOW RANGE VALUE
 in % is displayed. 
NOTE:  When Input Type (R_SP or S_90) is selected, Input 
Hi is not configurable.