Panasonic CU-UE12HKE Benutzerhandbuch

Seite von 45
20
B
A
Wall
Wall
More than 450 mm
More than 450 mm
Screw
219 mm
125 mm
Installation plate
Measuring
tape
224 mm
150 mm
2
1
Wall
Indoor
Outdoor
15 mm
Sleeve for
tube ass
’y
Approx. 5 - 7 mm
Bushing for tube ass
’y
Putty or caulking compound
Ø 70 through hole
10.2 Indoor Unit
10.2.1
How to Fix Installation Plate
The mounting wall is strong and solid enough to prevent if from the vibration.
The centre of installation plate should be at more
than 450 mm at right and left of the wall.
The distance from installation plate edge to
ceiling should more than 75mm.
From installation plate left edge to unit
’s left side
is 98mm.
From installation plate right edge to unit
’s right
side is 112mm.
B
: For left side piping, piping connection for gas should be about 45mm from this line.
: For left side piping, piping connection cable should be about 800mm from this line.
1 Mount the installation plate on the wall with 5 screws or more. (If mounting the unit on the wall, consider
using anchor bolts.) Always mount the installation plate horizontally by aligning the marking-off line with
the thread and using a level gauge.
2 Drill the piping plate hole with
ø70mm hole-core drill.
2.1
Line according to the left and right side edge of the installation plate. The meeting point of the
extended line is the centre of the hole. Another method is by putting measuring tape at position
as shown in the diagram above. The hole centre is obtained by measuring the distance namely
150mm and 125mm for left and right hole respectively.
2.2
Drill the piping plate hole at either the right or left and the hole should be slightly slanted to the
outdoor side.
10.2.2
To Drill a Hole in the Wall and Install a Sleeve of Piping
1
Insert the piping sleeve to the hole.
2
Fix the busing to the sleeve.
3
Cut the sleeve until it extrudes about 15mm from the wall
4
Finish by sealing the sleeve with putty or caulking compound at the
final stage.
Caution
When the wall is hollow, please be sure to use the sleeve for tube
ass
’y to prevent dangers caused by mice biting the connecting
cable.