Trinamic 11-0011 TMCM-171 BLDC Output For 3-phase BLDC Motors 11-0011 Datenbogen

Produktcode
11-0011
Seite von 134
TMCM-171 Manual (V0.92 / Nov 7th, 2007) 
 
17 
Copyright © 2007, TRINAMIC Motion Control GmbH & Co. KG 
 
5.4  Hall sensor only operation w/o encoder 
The module can be used without an encoder. In this case, set the encoder resolution parameter (SGP 
250) to the hall sensor resolution, i.e. 3 times the number of motor poles. Example: For a 4 pole 
motor set the encoder resolution to 12. To avoid oscillations in positioning mode, the algorithm in 
this mode stops regulation, as soon as the target distance is below the setting as determined by 
“MVP target reached distance”. Adapt this setting to your needs. Switch the module to hall sensor 
based commutation permanently in order to skip encoder initialization procedure in this configuration. 
Please be aware, that the hall sensor resolution is very low, when compared to an encoder, and thus, 
the PID regulator parameterization values have to be set much higher than the default setting. 
Without encoder, the velocity measurement is not available. You may want to set a lower value than 
the default for the “PWM Hysteresis” setting to get a softer response upon target reaching. 
5.5 Stop 
switch 
For positioning applications, typically some kind of global initialization is required. This can either be 
done via a central unit operating the motor via its bus interface, or a reference switch can be 
connected to the stop input (pull down to 0V at reference point). The position counter can be 
automatically cleared when this point is reached. Be careful not to apply a voltage different from GND 
to this digital input! 
 
5.6  General Functions (explore using the Windows based 
demo software) 
The TMCM-171 module can either be remote controlled via the PC demonstration software or a user 
specific program. The function of the stand alone mode can be modified by the user by writing 
initialization values to the on-board EEPROM, e.g. a maximum rotation velocity, motor current limit 
and rotation direction. For more detailed software information refer to the TMCM-170 Module – 
Reference and Programming Manual (see 7: References). 
 
5.7  Temperature, Current and Voltage monitoring functions 
Name 
LED / Output 
Action 
Meaning 
PWR 
Power 
On 
At least +5V power supply 
Current Limit 
Blink 
The current limit LED blinks upon under voltage switch 
off 
CL 
Current Limit 
On / Flicker 
Motor PWM is reduced due to exceeding the set motor 
current limit or overvoltage threshold is exceeded 
Temperature 
Warning 
Blink 
The power stage on the module has exceeded a critical 
temperature of 85°C.  (Pre-warning) 
TEMP 
Temperature 
Warning 
On 
The power stage on the module has exceeded a critical 
temperature of 115°C.  The motor becomes switched 
off, until temperature falls below 105°C. The 
measurement is correct to about +/-10°C 
Table 5.1: Temperature, Current and Voltage monitoring functions (LEDs)