7.2 External Signalling Device Connection
A maximum of two 8 Ohm signalling 
devices / speakers can be connected
in parallel to the terminal clamps 4 (-)
and 5 (+).
7.3 Relay Contact (N.O.)
The connection terminals 6 (+) and 
7
(-) are a relay contact (N.O. – normal-
ly open). The relay contact can be set
for timing mode or latch mode. This
can be determined by jumper C 
(s.
chapter 9: Jumper function)
Timing Mode: The relay contact is
reset 3 minutes after an alarm was
triggered.
Latch mode: The relay contact remains activated after an alarm was triggered, until
the system is reset.
Optical or acoustic signalling devices can be connected. 
Relay contact: 12V/DC, max. 5 ampere
7.4 Operating Voltage Connection (12-16V/DC)
The operating voltage (12-16V/DC) 
is connected to the terminal clamps 
7 (-) and 8 (+). 
Activate the operational voltage only after completing all connections.
1
2
3
4
5
6
7
8
9
10
11 12
+
12VDC/500MA
MIN. POWER
ADAPTOR
+
12V
BATTERY
+
OR
+
1
2
3
4
5
6
7
8
9
10
11 12
12V DC
BELL
STROBE LIGHT
OR OTHER
ALARM DEVICE
+
HORNS
+
8
8
1
2
3
4
5
6
7
8
9
10
11 12
30