PART 9 – START-UP PROCEDURE 
 
FOR YOUR OWN SAFETY READ BEFORE OPERATING 
 
1. This water heater does not have pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light 
the burner by hand. 
 
2. BEFORE OPERATING: smell all around the water heater area for gas. Be sure to smell next to the floor because some gas is 
heavier than air and will settle on the floor. 
WHAT TO DO IF YOU SMELL GAS 
 
Do not try to light any water heater.  
 
Do not touch any electric switch; do not use any phone in your building.  
 
Immediately call your gas supplier from a neighbor's phone. Follow the gas suppliers' instructions.  
 
If you cannot reach your gas supplier, call the fire department.  
 
Turn off gas shutoff valve (located outside of the water heater) so that the handle is crosswise to the gas pipe. If the handle will 
not turn by hand, don't try to force or repair it, call a qualified service technician. Force or attempted repair may result in a fire 
or explosion.  
 
4. Do not use this water heater if any part has been under water. Immediately call a qualified service technician to inspect the water 
heater and to replace any part of the control system and any gas control that has been damaged. 
 
5. The water heater shall be installed so the gas ignition system components are protected from water (dripping, spraying, rain, etc.) 
during water heater operation and service (circulator replacement, condensate trap, control replacement, etc.) 
 
Failure to follow these instructions could result in property damage, serious personal injury, or death. 
A. OPERATING INSTRUCTIONS 
If you smell gas, STOP. Follow listed safety instructions above. If you do not smell gas, follow the next steps. 
 
1. Make sure tank is full with cold water and purge all piping. To assure adequate purging, open all hot water faucets. 
 
 
Ensure the water heater is full of water before firing the burner. Failure to do so will damage the heater. Such damage IS NOT covered 
by warranty, and could result in property damage, serious personal injury, or death. 
 
2. Turn on all electric power to water heater. 
 
3. Remove the Front Panel WARNING label.  
 
4. Adjust the temperature set point of the heater to the desired level. The factory default setting is 
120
oF. If changes are necessary, follow “Overall Water Heater and Control Operation” in this 
section. 
 
5. If the water heater fails to start, refer to the Troubleshooting section in the back of this manual. 
B. TEST MODE 
Test mode is enabled by pressing 
 and 
 together for 5 seconds. In this mode the water 
heater operates without modulation, and the combustion system initially runs at the maximum fan 
speed. The SERVICE symbol is displayed on the LCD when Test mode is active. 
 
  
 
RESISTANCE TABLE FOR 
SUPPLY TEMPERATURE SENSOR 
HIGH/LOW TEMP. 
SENSOR TEMP. 
(
o
F) 
RESISTANCE 
(ohms) 
32 
32550 
41 
25340 
50 
19870 
59 
15700 
68 
12490 
77 
10000 
86 
8059 
95 
6535 
104 
5330 
113 
4372 
122 
3605 
131 
2989 
140 
2490 
149 
2084 
158 
1753 
167 
1481 
176 
1256 
185 
1070 
194 
915 
202 
786 
212 
667 
Table 14