Seahawks Post LDRA6 Benutzerhandbuch

Seite von 30
User Guide: LDRA6 
Chapter 2: Connections & Settings 
5 970 
484-6510 
www.rletech.com 
2-1.1  TB1 – Power 
The LDRA6 connects to a 24VDC power supply using TB1, a two position connector labeled 24VDC.   
2-1.2  POW1 – Power 
Power can also be supplied to the unit through POW1.  This is a wall adapter plug connection.  This also 
requires 24VDC. 
2-1.3  TB2, TB3 – Zone Inputs 
SeaHawk Leak Detection Cable (SC) and/or dry contact wires connect to the LDRA6 through TB2.  Fifteen 
foot (4.57m) leader cables (one is included in each leader cable kit, part #LC-KIT) are required for leak 
detection cable connections only.  Dry contact wires must be user supplied or may be supplied with your 
dry contact device.  Connect cables/wires as follows: 
Position  
Leak Detection Cable 
Dry Contact Wire 
TB3-1    
Zone 1 White 
 
Zone 1 Input-1 
TB3-2    
Zone 1 Black 
 
Zone 1 Input-2 
TB3-3    
Zone 1 Green 
 
N/A 
TB3-4 
 Zone 
Red 
 N/A 
TB3-5   
Zone 2 White 
 
Zone 2 Input-1 
TB3-6 
 Zone 
Black 
 Zone 
Input-2 
TB3-7   
Zone 2 Green 
 
N/A 
TB3-8 
 Zone 
Red 
 N/A 
TB3-9   
Zone 3 White 
 
Zone 3 Input-1 
TB3-10 
 Zone 
Black 
 Zone 
Input-2 
TB3-11   
Zone 3 Green 
 
N/A 
TB3-12 
 Zone 
Red 
 N/A 
 
TB2-1   
Zone 4 White 
 
Zone 4 Input-1 
TB2-2 
 Zone 
Black 
 Zone 
Input-2 
TB2-3   
Zone 4 Green 
 
N/A 
TB2-4 
 Zone 
Red 
 N/A 
TB2-5   
Zone 5 White 
 
Zone 5 Input-1 
TB2-6 
 Zone 
Black 
 Zone 
Input-2 
TB2-7   
Zone 5 Green 
 
N/A 
TB2-8 
 Zone 
Red 
 N/A 
TB2-9   
Zone 6 White 
 
Zone 6 Input-1 
TB2-10 
 Zone 
Black 
 Zone 
Input-2 
TB2-11   
Zone 6 Green 
 
N/A 
TB2-12 
 Zone 
Red 
 N/A 
2-1.4  TB5, TB4 – Zone Alarm Relays 
These are the Zone Alarm Relay output terminal blocks (Form C).  A status LED is located above each 
relay, which will indicate the state of the relay (on/off).  These relays can be configured as supervised or 
unsupervised, latched or unlatched (unsupervised and unlatched by factory default).  Connect the Zone 
Alarm Relay wires to TB3 and TB4 as follows: 
 
TB5-1 Zone 1 alarm relay normally open (NO) 
TB5-2 Zone 1 alarm relay common (C) 
TB5-3 Zone 1 alarm relay normally closed (NC)  
 
TB5-4 Zone 2 alarm relay normally open (NO) 
TB5-5 Zone 2 alarm relay common (C)  
TB5-6 Zone 2 alarm relay normally closed (NC)