APPENDIX A: MODBUS COMMUNICATIONS 
This document describes the Modbus communications protocol as supported by the LDRA6. It includes 
details and information on how to configure the LDRA6 for communications via Modbus network. 
A-1 
MODBUS IMPLEMENTATION OF THE LDRA6 
The LDRA6 is capable of communicating via the half-duplex RS485 serial communication standard.  The 
LDRA6 is configured to act as a slave device on a common network.  The RS485 medium allows for 
multiple devices on a multi-drop network.  The LDRA6 is a slave only device and will never initiate a 
communications sequence. 
A-1.1  Modes of Transmission 
The Modbus protocol uses ASCII and RTU modes of transmission.  The LDRA6 supports only the RTU 
mode of transmission, with 8 data bits, even, odd or no parity and one stop bit. 
Every Modbus packet consists of four fields: 
ƒ
 
Slave Address Field 
ƒ
 
Function Field 
ƒ
 
Data Field 
ƒ
 
Error Check Field (Checksum) 
A-1.1.1  Slave Address Field 
The slave address field is one byte in length and identifies the slave device involved in the transaction.  
Valid address range is between 1 and 254.  SW2 on the LDRA6 board sets the address.  The firmware 
program constantly reads dip SW2.  Any changes are updated on the fly.  Close the SW2 positions that 
correspond to the binary number of the address.  
A-1.1.2  Function Field 
The function field tells the LDRA6 which function to perform. Function codes are designed to invoke a 
specific action by the LDRA6.   
A-1.1.3  Data Field 
The data field varies in length depending on whether the message is a request or a response to a packet.  
This field typically contains information required by the LDRA6 to perform the command specified or to 
pass back data to the master device.   
A-1.1.4  Error Check Field 
The error check field consists of a 16-bit (2 byte) Cyclical Redundancy Check (CRC16).  It allows the 
LDRA6 to detect a packet that has been corrupted with transmission errors.