Chapter 1: Product Overview 
User Guide: LDRA6 
www.rletech.com 970 
484-6510 
CHAPTER 1: PRODUCT OVERVIEW  
1-1 
DESCRIPTION  
The LDRA6 is a complete monitoring system that detects and reports the presence of water and other 
conductive liquids, as well as monitors dry contact alarm points.   The LDRA6 couples SeaHawk Water 
Leak Detection Cable (SC) with an advanced control head to monitor six individual zones.  When a 
conductive liquid comes in contact with the SC cable, an alarm sounds and the summary alarm relay and 
zone relay activate.  The LED that corresponds with the appropriate zone also illuminates and an audible 
alarm is activated.  Each LDRA6 input can also be configured to detect a dry contact’s change of state (NO 
or NC
) and annunciate the alarm on the front panel. 
 
The LDRA6 is a supervised system - it continuously monitors the cable for leaks and cable integrity.  A 
cable break causes a cable fault indication.  An alarm sounds and the appropriate zone relay and the 
summary alarm relay activate.  The appropriate LED changes to indicate a cable fault has occurred.  
 
The dry contact relays in the LDRA6 may be configured as supervised or unsupervised (see section 2-2 for 
configuration options
).  Each zone can be configured with unique, individual settings.  When the user 
specified alarm condition occurs, the LDRA6 activates the appropriate relay and alarm LED. 
 
 
 
1-2 
LDRA6 FRONT PANEL INDICATORS  
1-2.1  Zone LEDs 
One tri-color LED for each zone. 
Default Leak Detection Cable Setting:  
On solid and green for normal cable conditions. 
Flashes quickly and turns red if a leak is detected in the zone. 
Flashes quickly and turns yellow if a cable fault is detected in the zone. 
On solid once an alarm is silenced. 
Default Dry Contact Setting:  
On solid and green for normal, non-alarm conditions. 
Flashes quickly and turns red (by default) if an alarm condition is detected in the zone. 
On solid once an alarm is silenced. 
1-2.2  Power LED 
On (green) as long as power is on. 
1-2.3  Audible Alarm 
Activates when an alarm condition is detected.  Silenced with the Quiet/Test/Reset switch. 
1-2.4  Quiet/Test/Reset Switch 
During alarm, the audible alarm is silenced, and any LED(s) in alarm will glow solidly.  If the alarm goes 
away, the LED(s) will flash slowly. Hold down the Quiet/Test/Reset switch to reset all alarms and 
complete and self test cycle.  If any alarms still exist, the unit will not reset the corresponding zones. 
 
NOTE
:   
The LDRA6 produces an alarm in the following conditions: 
ƒ
  Leak Detected 
ƒ
  Cable Fault 
ƒ
  Dry Contact Alarm Condition (User Specified)