F3200 Installation & Programming Manual
Document No: LT0122
New Zealand Operation
Page 12-6
5 July 2001
 
Issue 2.7
PROGRAMMABLE OPTIONS (CONTINUED)
(d) Daily battery test
This is enabled by default.  When enabled, every 24 hours (beginning at the auto test
start time) the charger voltage is reduced for 40 minutes and the battery voltage is 
monitored.
Parameter Defaults for New Zealand Mode
The following is a list of the values set when New Zealand mode is enabled by a database
re-initialise or when New Zealand mode is manually enabled.
New Zealand Display Extender fitted
- as appropriate
Battery very low alarm
- disabled
Evac defect is fault
- enabled
External defect is fault
- enabled
Battery low monitor
- enabled
Battery connection test
- enabled
Hourly battery test
- disabled
Daily battery test
- enabled
Charger fault monitoring
- disabled
Mains fail = fault after 8 hours
- disabled
MCP
- disabled
Alarm buzzer
- enabled
Zone and system fault buzzer
- disabled
Daylight saving start and end time
- enabled
The daylight saving start time for New Zealand is set to 2am on the first Sunday in October
and the end time is set to 2am on the third Sunday in March.
12.5 LOGIC 
TOKENS
The full list of logic tokens is given in Section 7.4.3.2.  Logic tokens that are valid only in
New Zealand mode are:
NSA
local silence alarms (this does not include any received network bells silence
State – refer BLI).
TEV
Local trial evac operated.
BSR
Local services restore operated.
NEV
Evac defect input asserted.
NED
External defect input asserted.