F3200 Installation & Programming Manual
Document No: LT0122
System Specifications
Page 3-8
5 July 2001
 
Issue 2.7
3.4 INPUT 
SPECIFICATIONS
3.4.1 AZC 
SPECIFICATIONS
General
Terminations
On 8 Zone Module, 2 per AZC.
Demountable screw terminal 1.5sq mm cable max.
Number
8 AZCs per 8 Zone Module.
64 max per system.
End of Lines  (EOLs)
Mode
EOL
1 Standard
2k7, 5%, 400mW resistor
2 High Current
2k7, 5%, 400mW resistor
3 Low Current
10k, 5%, 400mW resistor
4 Tamper
EOL002B active EOL
5 Disabled
None
Circuit Resistance & Capacitance
Mode
Capacitance
Resistance
1, 2 & 4
500nF
50 Ohm max
3     
1000nF
800 Ohm max for B2 Alarm
2k Ohm max for B3 Alarm
Voltages
Min
Typ
     Max
Detector Supply 
on MAF/PSU (note 1)
21.2V
22.0V      22.2V
     
(21.8V)
at AZC terminals
18.75V
20.3V      22.1V
at end of circuit
18.0V       
20.3V      22.1V
Alarm Voltage Thresholds
Band B3 upper threshold
17.2V
17.5V      17.8V
Band B3 lower threshold
12.75V
13.1V      13.45V
Band B2 upper threshold
Band B2 lower threshold
2.7V
2.9V
      3.1V
Band B1 upper threshold
Band B1 lower threshold
0V
0V
        0V