New Buck Corporation 42 Benutzerhandbuch

Seite von 52
VENTILATION AIR
 
VENTILATION AIR FROM INSIDE BUILDING 
This fresh air would come from an adjoining unconfined space.  When venting to an adjoining space, 
you must provide two permanent openings:  one within 12" of the ceiling  and one within 12" of the 
floor on the wall connecting the two spaces. (See Options 1 and 2 )  You can also remove door into 
adjoining room. (See Option 3 ) 
 
WARNING
 
REWORK WORKSHEET, ADDING THE SPACE OF THE ADJOINING UNCONFINED 
SPACE.  THE COMBINED SPACES MUST HAVE ENOUGH FRESH AIR TO SUPPLY ALL 
APPLIANCES IN BOTH SPACES. 
 
NOTE:   Each opening shall have a minimum free area of 1 square inch per 1000 BTU’s per hour of the 
total input ratings of all gas utilization equipment in the confined space, but not less than 100 square 
inches. 
Figure 6 Ventilation Air From Inside Building
 
   A.  Rework worksheet, adding the space of an adjoining room.  If the extra space provides an 
unconfined space, remove door to adjoining room or add ventilation grills between rooms.  See 
“Ventilation Air From Inside Building”, figure 6. 
   B.   Vent room directly to the outdoors.  See “Ventilation  Air From Outdoors”, page 16. 
   C.  Install a lower BTU/Hr heater, if lower BTU/Hr size  makes room unconfined. 
 
If  the  actual BTU/Hr used is less than the maximum  BTU/Hr  the space  can support, the 
space is an unconfined space.   You  will need no additional fresh air ventilation. 
WARNING:   
YOU MUST PROVIDE ADDITIONAL VENTILATION AIR  IN A 
CONFINED SPACE 
Page 15