Weil-McLain RLS Datenbogen

Seite von 4
Weil-McLain 88 Water and Steam Boilers — Series 2 — 
For Gas, Light Oil, & Gas/Light Oil-Fired Burners
2
Part No. 550-142-023/0508
Burner data — #2 Fuel oil/Natural gas — Modulating
Table 1 
Boiler 
Model 
Number
Burner 
Model 
Number
Pressure 
Drop Thru 
Gas Train
Manifold 
Pressure
Gas Pressure 
Required at  
Gas Control 
Inlet
Gas Pilot 
Pressure
Combustion 
Head 
Setting
Combustion 
Air 
Indications
Servo Motor Cam  
Position Settings
Oil  
Nozzles
Oil 
Pressure  
Fuel 
Independent 
Motor Driven 
3450 RPM
Inches 
W.C.
Inches 
W.C.
Inches 
W.C.
Min
Inches 
W.C.
Max
Inches 
W.C.
Low 
Fire
High 
Fire
Blue Orange Red 1
2
3
4
5
6 Qty.
GPH 
@ 100 
PSIG
Brand Type Spray 
Angle
Supply 
PSIG
Suntec 
Type
Gear 
GPH
488R RLS28
1.19
4.60
5.79
14
5.0
1
23
67
22
42
70 — — — — — —
1
1
2.75
2.50 Delavan B
70°
60°
180
AL65C 22.0
488
RLS28
1.19
4.85
6.04
14
5.0
2
23
67
22
42
70 — — — — — —
1
1
3.00
2.50 Delavan B
70°
60°
180
AL65C 22.0
588
RLS38
1.88
5.85
7.73
14
5.0
1
20
50
19
41
55 — — — — — —
1
1
4.00
3.50 Delavan B
60°
60°
167
AL65C 22.0
688
RLS50
2.09
5.88
7.97
14
5.0
3
32
90
32
50
90 — — — — — —
1
1
4.50
5.00 Delavan B
60°
60°
173
AL65C 22.0
788
RLS50
2.12
5.85
7.97
14
5.0
5
35
83
35
45
83 — — — — — —
1
1
5.50
6.00 Delavan B
60°
80°
168
AL65C 22.0
888
RLS70
3.04
4.36
7.40
14
7.5
0
1.5
6.0
— 130 0
40 120 30 100 11
6.50
6.50 Delavan B
90°
60°
180
AJ4CC 52.5
988R RLS70
3.18
4.14
7.32
14
7.5
0
1.8
7.5
— 130 0
40 120 27 100 11
7.50
7.25 Delavan B
90°
60°
180
AJ4CC 52.5
988
RLS70
3.18
4.39
7.57
14
7.5
1
1.8
7.5
— 130 0
40 120 27 100 11
7.50
7.50 Delavan B
60°
60°
180
AJ4CC 52.5
1088R RLS70
3.35
3.68
7.03
14
7.5
3
1.9
9.0
— 130 0
32 120 45 100 11
8.50
7.25 Delavan B
60°
60°
209
AJ4CC 52.5
1088 RLS100
3.35
3.93
7.28
14
7.5
4
1.9
9.0
— 130 0
32 120 45 100 11
8.50
7.50 Delavan B
60°
60°
209
AJ4CC 52.5
1188 RLS100
3.55
4.45
8.00
14
6.0
4
2.2
5.2
— 130 0
30 120 35 100 11
9.00
9.00 Delavan B
60°
60°
180
AJ4CC 52.5
1288 RLS100
2.60
5.30
7.9
14
6.0
4
2.0
6.0
— 130 0
30 120 40 100 11
10.00
10.00 Delavan B
60°
60°
180
AJ4CC 52.5
1388 RLS100
3.35
4.65
8.00
14
6.0
9
2.0
6.5
— 130 0
30 120 40 100 11
11.00
11.00 Delavan B
60°
60°
200
AJ4CC 52.5
1488 RLS130
2.81
4.54
7.35
14
6.0
6
2.0
6.0
— 130 0
40 120 55 100 11
12.00
12.00 Delavan B
60°
60°
200
AJ4CC 52.5
1588 RLS130
2.99
4.65
7.64
14
5.5
7
2.5
7.0
— 130 0
40 120 30 100 11
12.00
12.00 Delavan B
60°
60°
220
AJ4CC 52.5
1688R RLS130
3.40
4.85
8.25
14
5.0
8
2.5
8.0
— 130 0
40 120 30 100 11
13.00
12.50 Delavan B
60°
60°
215
AJ4CC 52.5
1688 RLS130
3.40
5.10
8.5
14
5.0
9
2.0
9.0
— 130 0
50 120 30 100 11
13.00
13.00 Delavan B
60°
60°
215
AJ4CC 52.5
Burner specifications and settings
Notes for Table 1, Table 2 and Table 3
Burner capacities listed for elevations up to 2,000 feet.  For higher eleva-
1. 
tions, consult local Weil-McLain distributor/ agent or sales office.
Light oil ratings based on No. 2 fuel oil with heating value of 140,000 
2. 
Btu per gallon.
Gas ratings based on natural gas with heating value of 1,000 Btu per cubic 
3. 
foot and specific gravity of 0.60.  Gas burners for other gases are available.  
Consult local Weil-McLain distributor/agent or sales office.
Boiler-burner unit to be adjusted to achieve +0.10 inches W.C. pressure at 
4. 
the flue collar, resulting in positive pressure in firebox as listed.
Minimum gas pressures listed are subject to variations due to job condi-
5. 
tions.  Gas burners for other gas pressures are available.  Consult local 
Weil-McLain distributor/agent or sales office.
All gas train sizes shown are based on a supply pressure to the regulator of 
6. 
7 inches w.c. Optional trains available for other pressures upon request.
All Settings and pressures shown are for initial start-up. Final values should 
7. 
be confirmed with combustion analysis.
Gas/Light Oil control Systems: 
8. 
LHL:  Low-high-low-off firing conditions – two position air and fuel 
controlled by separate motor, open damper pre-purge. 
MOD:  On-off operation with proven low fire start and full modu-
lating firing conditions.  Proportional motor drives fuel metering 
valve  and  combustion  air  damper  according  to  firing  conditions; 
open damper pre-purge.
120/60/1 control circuit is used for all burners.
9. 
All 3 phase models require a separate 12/60/1 control voltage supply.
10. 
Burner settings shown are for initial start-up.  Follow burner manual to 
11. 
adjust burner using combustion test instruments as directed.
120/60/1 control circuit is used for all burners.
12. 
488R to 788 units require a single SPDT controller for LHL firing rate 
13. 
operation on both fuels.
888 to 1688 units require a 4 – 20mA 0 – 10vdc or 135 ohm signal for 
14. 
modulation on gas plus a SPDT controller for LHL firing rate operation 
on oil.
Motor relay or contactor is standard on all units.
15. 
Combustion Controls:
16. 
Siemens LFL 1.335 flame safeguard control monitors the oil or gas 
burner flame with visual diagnostic window, provides pre-purge and 
post purge, provides switching necessary to allow firing rate motor to