Hardware and Connectivity  35
Power Supply Specifications
highest voltage at some point, in which case the unit will switch to it. No power loss will 
occur during a switch over.
DC Power Requirements
HV and DHV models:
The IOLAN can be powered via a DC source. The following are the ranges for the DC voltage 
supported by the unit;
Minimum: 88 VDC
Nominal: 125-250 VDC
Maximum: 300 VDC
The DC supply(s) should have adequate over-current protection within the closed rack system 
and comply with local or national standards applicable to the installation territory. 
You need wire gauge 14 to 18AWG to connect the IOLAN rack mount unit to the power source.
LDC models:
The IOLAN can be powered via a DC source. The following are the ranges for the DC voltage 
supported by the unit;
Minimum: 18 VDC
Nominal: 24-60 VDC
Maximum: 72 VDC
You need wire gauge 12 to 18AWG to connect the IOLAN rack mount unit to the power source.
AC Power Requirements
HV and DHV models;
The IOLAN can be powered via an AC source. The following are the ranges for the AC voltage 
supported by the unit.
Minimum: 85 VAC
Nominal: 100-240 VAC
Maximum: 265 VAC
You need wire gauge 14 to 18AWG to connect the IOLAN rack mount unit to the power source.
TELCO-NEBS Models
LDC models:
The IOLAN can be powered via a DC source. The following are the ranges for the DC voltage 
supported by the unit;
Minimum: 18 VDC
Nominal: 24-60 VDC
Maximum: 72 VDC
The Battery Return input terminals of the IOLAN can support either Isolated DC return (DC-I) 
or Common DC return (DC-C). 
You need wire gauge 12 to 18AWG to connect the IOLAN rack mount unit to the power source.
Note:
The equipment must be grounded for safety and to ensure ESD protection for correct 
operation and protection of the internal circuitry.
Note:
The equipment must be grounded for safety and to ensure ESD protection for correct 
operation and protection of the internal circuitry.