Trane CAH-SVX01A-EN Benutzerhandbuch

Seite von 60
Installation
24
 CAH-SVX01A-EN
Duct Connections
All duct connections to the units 
should be installed in accordance 
with the standards of the National 
Fire Protection Association (NFPA) 
for selecting and installing of air 
conditioning and ventilating 
systems other than residence type 
(NFPA 90A), and residence type 
warm air heating and air 
conditioning systems (NFPA 90B).
To ensure the highest fan efficiency, 
duct turns and transitions must be 
made carefully, minimizing air 
friction losses and turbulence. 
Proper duct work installation by such 
organizations as SMACNA (Sheet 
Metal and Air Conditioning 
Contractors National Association, 
Inc.) should be adhered to. 
Component 
Installation 
Requirements
Each component in the Custom air 
handler may have installation 
requirements that could affect the 
unit’s performance.
Note: For components included in 
the unit but not included in this 
manual, reference the component 
manufacturers specific Installation, 
Maintenance, and Operation 
manual. Copies of these manuals 
are either included in the package 
with this unit IOM or are attached to 
the components mounted in the 
unit.
Fans
The fan and motor assembly are 
internally isolated. The fan and 
motor bases are bolted to a 
minimum of four spring isolators. 
The isolators are secured to the fan 
section support base. Shipping tie-
down blocks are bolted to the 
isolators between the fan base and 
the isolator support frame.
To activate the isolation, remove the 
shipping tie-down blocks. Retain 
these blocks for use in adjusting 
isolators if necessary.
Isolator Adjustment
Note: Isolators are pre-adjusted and 
set at the factory. Follow this 
procedure only if necessary and as it 
applies to the isolators used in this 
unit. This procedure, for isolators 
can, and should be, performed by 
one person to ensure that the proper 
sequence is followed.
Isolators are selected for distribution 
of equipment weight, but may not all 
compress the same. This procedure 
assumes the base surface is level. 
Isolators are not intended to be 
leveling devices.
1
Verify that the shipping bolts that 
hold the fan base in a fixed 
position have been removed.
2
Remove the jam nut on top of the 
isolator adjusting stud at the first 
isolator to be adjusted. Check 
that the shipping block is in 
place.             
Figure 19. Isolator
 
SHIPPING TIE-
DOWN BLOCK 
(SHIM ) 
ADJUSTING 
NUT 
JAM  NUT 
SHIPPING 
BOLT 
FAN BASE 
 WARNING
Hazardous Voltage with 
Capacitors!
Disconnect all electric power, 
including remote disconnects and 
discharge all motor start/run 
capacitors before servicing. Follow 
proper lockout/tagout procedures to 
ensure the power cannot be 
inadvertently energized. For variable 
frequency drives or other energy 
storing components provided by 
Trane or others, refer to the 
appropriate manufacturer’s 
literature for allowable waiting 
periods for discharge of capacitors. 
Verify with an appropriate voltmeter 
that all capacitors have discharged. 
Failure to disconnect power and 
discharge capacitors before 
servicing could result in death or 
serious injury. 
Note: For additional information 
regarding the safe discharge of 
capacitors, see PROD-SVB06A-EN.
Turn the adjusting nut 2 or 3 turns 
only, counterclockwise on each 
isolator in a sequenced manner. The 
equipment weight will compress the 
spring inside the housing 
approximately 1/4 inch.