Trane OABE OADE OAKE OANE (Water Source Heat Pump) Katalog

Seite von 67
62
 OAU-PRC003A-EN
Mechanical Specifications
Options
Electric Heating Option
Primary heat is supplied using Electric Resistance heaters. Heaters shall meet the requirements of 
the National Electrical Code and shall be listed by Underwriters Laboratories for zero clearance to 
combustible surfaces and for use with heat pumps and air conditioning equipment. Heating 
elements shall be open coil, 80 percent nickel, 20 percent chromium, Grade A resistance wire. 
Type C alloys containing iron or other alloys are not acceptable. Coils shall be machine crimped into 
stainless steel terminals extending at least 1 inch into the air stream and all terminal hardware shall 
be stainless steel. Coils shall be supported by ceramic bushings staked into supporting brackets. 
Heater frames and terminal boxes shall be corrosion resistant steel. Unless otherwise indicated, 
the terminal box shall be NEMA 1 construction and shall be provided with a hinged, latching cover. 
Heaters shall be furnished with a disc type, automatic reset thermal cutout for primary over 
temperature protection. All heaters shall also be furnished with disc type, load-carrying manual 
reset thermal cutouts, factory wired in series with heater stages for secondary protection. Heat 
limiters or other fusible over temperature devices are not acceptable. Control will be SCR type. Unit 
shall be suitable for use with Electric Resistance Heat. Refer to 
.
Gas-Fired Heating Option
Primary heat is supplied using indirect fired gas heating. The heating section shall have a 
progressive tubular heat exchanger design using stainless steel burners and Type 409 stainless 
steel tubes. An induced draft combustion blower shall be used to pull the combustion products 
through the firing tubes. The heater shall use a direct spark ignition (DS) system. On initial call for 
heat, the combustion blower shall purge the heat exchanger for 20 seconds before ignition. After 
three unsuccessful ignition attempts, the entire heating system shall be locked out until manually 
reset at the thermostat/zone sensor. Units shall be comply with the California requirement for low 
NO
x
 emissions. Unit shall be suitable for use with Natural Gas.
Figure 48.
ER Heater