Install Outdoor Unit 
 
 
Power Cable Connection
 
 
1.  Remove the handle at the right side plate of the outdoor unit 
(one screw). 
2.  Remove the cable clamp, connect the power connection cable 
with the terminal at the row of connection and make the 
connection. The fitting line distributing must be consistent 
with the indoor unit. 
3.  Use cable clamp to make the cable connection cable. 
4.  Confirm the fitting lines are properly installed. 
5.  Install the handle (fixed by one screw). 
 
Notes: 
•  Improper line connection may cause failure of some electrical 
components and parts 
•  When fixing the cable, a certain degree of play shall be 
maintained for the cable between the connection point and the 
fixing point. 
 
Vacuum – Pumping and Leakage Inspection
 
 
1.  Remove the nut cover at the shutoff valve. 
2.  Align with the center of the fitting pipe and manually 
tighten the conical nut sufficiently. 
3.  Use spanner to tighten the conical nut. 
4.  Remove the liquid valve cap, the gas valve cap and the 
nut of refrigerant charging mouth. 
5.  Use inner hexagon spanner to twist off the liquid valve 
body and at the same time use screwdriver to open the valve 
core of the liquid valve. Now gas shall flow out. 
6.  After gas continues flowing out for about 15 second and 
refrigerant gas begins to flow out, close the valve core and 
tighten the nut of refrigerant charge mouth. 
7.  Completely open the valve body of the liquid valve and the 
gas valve. (See Fig 12) 
8.  Turn and tighten the valve cap, then use soap water or a leak 
detector to check if there is gas leakage at the outdoor and 
indoor units and the pipeline connections. 
9.  If conditions permit, use a vacuum pump to exhaust air in 
the unit from the valve core. (See Fig 13) 
 
Draining of Condensate Water of Outdoor Unit
 
 
When the air-conditioning unit is in the heating mode, the 
condensate water generated at the outdoor unit and the water 
generated by defrosting shall be drained through the drainage 
pipe to proper place. 
 
Installation methods: As shown in Figure, insert the drainage 
joint of the outdoor unit into the Φ25 hole on the base plate.  
Connect the drainage pipe to the drainage mouth so as to drain 
the condensate water and water generated by defrosting to 
proper place.