Hoshizaki 73168 Benutzerhandbuch
22
Service
Menu
Menu
Item and Details
Setting Range
Factory Default
Cabinet
Rail
Cabinet
Rail
F0
Defrost Interval
• The cabinet uses a time initiated
• The cabinet uses a time initiated
heated defrost.
• The change in the defrost
interval setting will take effect
immediately. The next defrost
will take place after the newly
set time interval has elapsed.
immediately. The next defrost
will take place after the newly
set time interval has elapsed.
• Initiating a manual defrost on the
cabinet will restart the defrost
timer.
timer.
1 to 12 hours in
1 hour increments.
N/A
6
N/A
F1
Defrost Termination Temperature
Do not adjust. For
recommendations, contact
Hoshizaki Technical Support.
Do not adjust. For
recommendations, contact
Hoshizaki Technical Support.
41 to 68°F
(5 to 20°C)
in 1 degree
increments
N/A
49°F (9.4°C)
N/A
F2
Setpoint Temperature Differential
Use "SET" button to scroll through
all 4 settings.
• You cannot set both + and ‑ to
Use "SET" button to scroll through
all 4 settings.
• You cannot set both + and ‑ to
0.0.
• Negative value indicated by LED
to left of number.
Both the + and - values can be
adjusted between 0 to 6.3°F in
increments of .9°F
(0 to 3.5°C in increments of .5°C)
(decimal not displayed)
adjusted between 0 to 6.3°F in
increments of .9°F
(0 to 3.5°C in increments of .5°C)
(decimal not displayed)
Comp on
0°F (0°C)
at setpoint
Comp off
-3.6°F (-2°C)
below setpoint
Comp on
0°F (0°C)
at setpoint
Comp off
-3.6°F (-2°C)
below setpoint
F3
High Temperature Alarm Delay
Time: See "III.A. Alarm Signals."
Time: See "III.A. Alarm Signals."
0 to 3 hours in 1 hour increments
2
F4
Low Temperature Alarm Delay
Time: See "III.A. Alarm Signals."
Time: See "III.A. Alarm Signals."
0 or 1 hour
1
F5
Temperature Display
Fahrenheit or Celsius
°F
F6
Alarm History: maximum 8 alarms.
No reset for alarm history
available.
available.
Alarms displayed newest to oldest.
When "‑‑" appears, you have
reached the end of the alarm
history.
When "‑‑" appears, you have
reached the end of the alarm
history.
N/A
F7
Compressor Run Time (%):
Displays compressor run time
percentage between the 2 most
recent defrosts.
Displays compressor run time
percentage between the 2 most
recent defrosts.
N/A
N/A
F8
Not Used
N/A
N/A
F9
Rail Cooling Switch:
"LOW" Rail Fan Adjustment (rail
section only)
"LOW" Rail Fan Adjustment (rail
section only)
0=rail fans on continuously (same
as "NORMAL" position)
1=rail fans on 15 sec.
rail fans off 90 sec.
2=rail fans on 1 sec.
rail fans off 90 sec.
as "NORMAL" position)
1=rail fans on 15 sec.
rail fans off 90 sec.
2=rail fans on 1 sec.
rail fans off 90 sec.
N/A
2
FA
Do not
adjust
High Condenser Temperature
Alarm Setting (clogged filter):
For recommendations, contact
Hoshizaki Technical Support.
Alarm Setting (clogged filter):
For recommendations, contact
Hoshizaki Technical Support.
Adjustable between 140 to 167°F
(60 to 75°C).
(60 to 75°C).
140°F (60°C)
(1 not displayed)
Fb
Audible Control
N/A
N/A
b) Service Menu Chart