Configuration, Startup, and Operation 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
113 
Table 4-16  Remote Switch Parameter Definitions 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
REMSW1 
 
 
 
NONE   [factory setting] 
SP2 
 
 
 
 
 
 
 
MAN 
 
 
 
 
MNFS 
 
 
 
 
 
 
HOLD 
 
 
RUN 
 
 
TIMR 
 
REMOTE SWITCH 1
—Use this parameter to specify 
what action the recorder should take if digital input 1 for 
this channel goes to ON (switch contact closed). 
NONE
—No remote switching action. 
SETPOINT2
—Controller setpoint used in Auto will go to 
the value of the second setpoint (operating parameter 
“S2” for the channel) when the digital input goes ON. 
(When it goes OFF, the recorder will resume using “SP” 
for the channel.) 
Use of the second setpoint with a remote switch is 
independent of the number of setpoints specified with 
control group parameter “NumSPs”. 
MANUAL
—Controller will be switched to Manual mode 
when the digital input goes ON. Output will not change 
until the operator changes it. (When the digital input goes 
OFF, the controller will go back to Auto, using operating 
parameter “SP” as the basis of computing output.) 
MANUAL WITH FAILSAFE
—Controller will be switched 
to Manual mode and the output will be changed to the 
value of control group parameter “FAILSF” for the 
channel when the digital input goes ON. (When the digital 
input goes OFF, the controller will go back to Auto, using 
operating parameter “SP”as the basis of computing 
output.) 
HOLD
—When the digital input goes ON, the recorder will 
hold execution of the single setpoint ramp or the optional 
setpoint program.  
RUN
—When the digital input goes ON, the recorder will 
start execution of the single setpoint ramp or the optional 
setpoint program.  
TIMER
—When the digital input goes ON, the optional 
timer will start. 
REMSW2 
NONE  [factory setting] 
SP2 
MAN 
MNFS 
HOLD 
RUN 
TIMR 
REMOTE SWITCH 2
—This parameter is used to specify 
what action the recorder should take if digital input 2 for 
this channel goes ON (switch contact closed). The 
choices are the same as for REMSW1.