Rosemount 4500
B-2
HAZARDOUS 
LOCATIONS 
CERTIFICATIONS
North American 
Certifications
Factory Mutual (FM) Approvals
I5
Intrinsically Safe for use in Class I, II, III, Division 1, 
Groups A, B, C, D, E, F, and G;
Temperature Code T4 (T
amb
 = 0 to 60°C); 
Intrinsically Safe for use in Class I, Zone 0 AEx ia IIC 
T4 (T
amb
 = 0 to 60°C); 
Non-incendive for Class I, Division 2, Groups A, B, C, and D; 
When connected in accordance with 
Rosemount drawing 04500-5001;
Enclosure Type 4X 
For entity parameters see control drawing 04500-5001;
Canadian Standards Association (CSA) Approvals (Pending)
I6
Intrinsically Safe for use in Class I, Division 1, 
Groups A, B, C, and D;
Temperature Code T3C (T
amb
 = 0 to 60°C);
Intrinsically Safe for use in Class I, Zone 0 Ex ia IIC 
T4 (T
amb
 = 0 to 60°C); 
When connected in accordance with 
Rosemount drawing 04500-5002; 
Enclosure Type 4X
For entity parameters see control drawing 04500-5002;
European Certifications
I1
ATEX Intrinsic Safety 
Certificate No. Baseefa05ATEX0091X
ATEX Marking:
 II 1 G 
EEx ia IIC T4 (T
amb 
= 60°C)
IP66
 1180
Input Parameters:
U
i
 = 30V
I
i
 = 200mA
P
i
 = 1.0W
C
i
 = 0nF
L
i
 = 2.4
μH
Special Conditions For Safe Use (x)
The plastic meter cover does not meet the surface resistivity requirements 
and, to avoid electrostatic charging, it must not be rubbed or cleaned with 
solvents.