Honeywell DCP200 User Manual

Page of 184
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Modbus Parameters
Page 91
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Digital Output 2B 
Function
2177
0x0881
R/W
Value
Digital Output 2B Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Output 2 or 2A 
Alarm Selection
2178
0x0882
R/W
Value
Output 2 or 2A Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Output 2B Alarm 
Selection
2179
0x0883
R/W
Value
Output 2B Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse